| Description of Equipment
The SmartNode is a highly versatile input/output (IO) controller. Many applications can be set up out of the box with minimal configuration options. The SmartNode can also be used for more custom sequences outside its typical terminal application profiles.
The SmartNode VAV Terminal Profiles (Series Fan with reheat, Parallel Fan reheat, No Fan with Reheat) are zone-level controllers that control a typical VAV box in a building.
Based on whether the system level equipment AHU or RTU is in cooling mode or Heating mode the damper and reheat operations enable to provide the optimum results for the zone based on the zone load.
The SmartNode VAV Terminal Profiles (Series Fan with reheat, Parallel Fan reheat, No Fan with Reheat) allow the choice of dampers, reheat based on the equipment used, and the zone priority which equates to the importance multiplier in guideline 36.
Quick Summary | |
Damper Control | Reset based on Space Temperature and/or CO2 and/or VOC and /or CFM & mode of operation. |
Reheat Control | Reset based on Space Temperature & mode of operation at the system level |
Fan Control |
Reset based on Reheat |
| Schematics
VAV No Fan with Electric Reheat
VAV No Fan with Modulating Reheat
VAV Series Fan with Electric Reheat
VAV Series Fan with Modulating Reheat
VAV Parallel Fan with Electric Reheat
VAV Parallel Fan with Modulating Reheat
| Control System Object List
Object Name | Type | Input/Output Type |
Heating Desired Temp | User Intent | NA |
Cooling Desired Temp | User Intent | NA |
Current Temp | Input | OWI Sensor |
Humidity | Input | OWI Sensor |
Occupancy Mode |
Input |
OWI Sensor |
Damper Actuator | Output | SmartNode Analog Out |
Reheat Stage 1 | Output | SmartNode Relay |
Reheat Stage 2 | Output | SmartNode Relay |
Modulating Reheat | Output | SmartNode Analog Out |
Zone Priority | Input | User Intent/ Configuration Setup |
Damper Size & Shape | Input | User Intent/ Configuration Setup |
Discharge Airflow Temperature | Input | SmartNode Thermistor |
Supply Airflow Temperature | Input | SmartNode Thermistor |
Minimum Damper Position Cooling | Input | User Intent/ Configuration Setup |
Maximum Damper Position Cooling | Input | User Intent/ Configuration Setup |
Minimum Damper Position Heating | Input | User Intent/ Configuration Setup |
Maximum Damper Position Heating | Input | User Intent/ Configuration Setup |
Minimum CFM Cooling | Input | User Intent/ Configuration Setup |
Maximum CFM Cooling | Input | User Intent/ Configuration Setup |
Minimum CFM Reheat | Input | User Intent/ Configuration Setup |
Maximum CFM Reheat | Input | User Intent/ Configuration Setup |
Maximum Damper Heating | Input | User Intent/ Configuration Setup |
reheatZoneMaxDischargeTemp | Tuner | 90 F |
coolingPreconditioningRate | Tuner | 15 Mins |
heatingPreconditioningRate | Tuner | 15 Mins |
Note: For a comprehensive list of tuners and their details refer to Tuners Complete List.
| Sequence of Operation
The sequence of operation is completely driven based on Occupancy mode, Space Current Temperature, the set Cooling and Heating Desired Temperatures, CFM, and Space CO2 & VOC levels.
Let us understand the Sequence of operations based on the occupancy modes, and how the other factors contribute to the sequence of operations during different types of occupancy modes.
| Occupancy Modes
The occupancy mode (Occupied or Unoccupied) shall be determined through a user-adjustable, graphical, seven-day schedule with a holiday schedule, alongside the configurable autoaway and forced occupied options (external schedule influencers) for optimized controls and enhanced energy savings.
Based on the above aspects factoring into the occupancy the following can be the possible applicable occupancy modes:
- Pre- Conditioning
- Occupied
- Unoccupied
- Auto-Away
- Forced Occupied
| Sequence of Operation During Pre-Conditioning
Pre-conditioning is a state just before the building enters the scheduled occupancy. It starts at more like the unoccupied state, the desired temperatures drift to unoccupied setbacks.
The preconditioning uses an algorithm to start the conditioning before the building is scheduled for occupancy, from the heating side or cooling side, to bring the building to an optimum level ( within the occupied heating & cooling desired temperatures) exactly at the time of occupancy start.
A coolingPreconditioningRate and heatingPreconditiningRate tuners defaulted to 15 minutes, are used alongside the occupied heating/cooling desired temperature breach to determine when the pre-conditioning should start.
Example Calculation:`
When,
- The heating & cooling desired temperatures are 70F and 74F for the building,
- The current temperature is 76F (Average of zone temperatures),
- 8:00 AM is the time the building is scheduled to be occupied.
Then the preconditioning start time is calculated as follows:
Cooling Desired Temperature Breach= 76-74=2F
Preconditioning duration= coolingPreconditioningRate (mins) * Cooling Desired Temperature Breach
= 15*2
= 30 mins
The preconditioning starts 30 minutes before the building is scheduled to be occupied, which is = 7:30 AM.
The zones would operate as shown below to accommodate the preconditioning from the system equipment.
During Warm-up:
- If the space temperature is below the occupied heating desired temperature, the space utilizes the warm-up via HeatingLoopOutput as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The Damper remains at a minimum |
The HeatingLoopOutput is mapped to the Damper position actuator For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 and IAQ loops are disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Pre-cooling:
- If the space temperature is below the occupied cooling desired temperature, the space utilizes the morning pre-cooling via CoolingLoopOutput, as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position |
- The CO2 and IAQ loops are disabled. (If configured for)
| Sequence of Operation During Occupied
At all occupied times: (based on a set schedule)
- The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
Configuration | Damper Operation |
If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & VOC-based configuration is enabled. |
The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
If zone Temperature, IAQ(CO2 & VOC) & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space current temperature falls below the HeatingDesiredTemperature the HeatingLoopOutput is enabled as below as below.
If System Equipment is in Cooling Mode | If System Equipment in Heating Mode |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation
|
During Cooling:
- When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled, as below
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
Note: The fan runs wherever the zone is occupied and when the reheat is enabled.
| Sequence of Operation During AutoAway
- The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
- The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
- CoolingLoopOutput, HeatingLoopOutput, CFM LoopOutput, CO2 and IAQ Loop Output, and Reheat Stages are disabled.
During Heating:
- When the space current temperature falls below the heating autoaway setback temperature, the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 and IAQ loops are disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current is above the cooling the CoolingLoopOutput is enabled, as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 and IAQ loops are disabled. (If configured for)
Note: The fan runs wherever the zone is occupied and when the reheat is enabled.
| Sequence of Operation During UnOccupied
- The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
- The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
Configuration | Damper Operation |
If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & VOC-based configuration is enabled. |
The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
If zone Temperature, IAQ(CO2 & VOC) & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space's current temperature falls below the heating the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 and IAQ loops are disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current temperature is above the cooling the CoolingLoopOutput is enabled, as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 and IAQ loops are disabled. (If configured for)
Note: The fan runs wherever the zone is occupied and when the reheat is enabled.
| Sequence of Operation During Forced Occupied
- The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
Configuration | Damper Operation |
If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & VOC-based configuration is enabled. |
The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
If zone Temperature, IAQ(CO2 & VOC) & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space current temperature falls below the Heating Desired Temperature the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 and IAQ loops are disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled as below,
If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 and IAQ loops are disabled. (If configured for)
Note: The fan runs wherever the zone is occupied and when the reheat is enabled.
| Sequence of Operation During Emergency Conditioning
When zone limits are violated, and the recorded temperature is within the zone limit plus leeway the conditioning will happen in the direction of zone load.
| Sequence of Operation Zone Temp Dead
And, When the zone temperature breaches the zone limits, beyond the leeway limits all the following loops are disabled:
- CoolingLoopOutput
- HeatingLoopOutput
- Reheat Stages
- FanLoopOutput
- CO2 & IAQ LoopOutput
- CFM LoopOutput
| Control Mode Summary
Modes & Operation |
Pre-Conditioning | Occupied | AutoAway | Unoccupied | Forced Occupied |
Auto |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput CFMLoopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput CFMLoopOutput CO2LoopOutput IAQLoopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
Heat Only |
HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
Cool Only |
CoolingLoopOutput FanLoopOutput CFMLoopOutout |
CoolingLoopOutput FanloopOutput CFMLoopOutput CO2LoopOutput IAQLoopOutput |
CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
Off |
All Loops Deactivated |
Note: FanLoopOutput/ Fan is applicable only for the VAV terminal profiles with series or parallel fans, and not for the VAV terminal profile with no fan.
Comments
0 comments
Please sign in to leave a comment.