The following details needed by a VTN provider for linking to a 75F VEN instantiation:
- VTN URL , VTN ID , VTN Name
- VEN ID, VEN Name
- VEN certificate details to be shared individually for each VEN setup: VTNs use the certificate fingerprint to identify a VEN.
- 75F VEN systems uses Signal type “Simple” with “level” option
- Level with 0 value for switching off the DR Mode
- Level value greater than 0 for initiating the associated 75F Building system into DR Mode
- This Simple Signal is listened to by 75F VEN on
- OnEvent
- OnEventStart
- OnEventComplete
- The mapping between VTN to VEN to 75F Buildings is maintained internally.
- Once the signal is triggered, the DR mode is started and stopped on the internal CCUs by 75F VEN.