| How it Works

In the 75F® system, HyperStat hardware product on the software side supports the Sense profile. This provides enhanced visibility of hyperstat equipment that is monitored by the 75F solution for various equipment. 

The HyperStat is a successor of the SmartStat,  with 8 onboard sensors, giving the advanced capability of the thermostat, humidistat, and IAQ sensing station with both modulating and staged equipment control. HyperStat provides monitoring and control of a wide variety of HVAC standalone equipment through its various relay stages or modulating analog outputs. 

Once the equipment has been configured, the sensed parameter configured shows up in zone settings screens across portals, apps, and CCU.

Only one hyper Stat module with a Sense profile can be paired to a single zone. 

There is no concept of building limit breach since it is only controlling a single room. There is no zone priority assigned as Sense profile in Hyperstat operation and it does not affect any central air handling HVAC equipment connected to the CCU. 

You can configure the following inputs that can be sensed. 

  • Temperature
  • Humidity
  • Co2 - CO2 widget
  • VOC - CO2 widget
  • Onboard Sensors - Sound, PM2.5, and Light - Sensor’s widget
  • Thermistor 1 - Thermistor widget
  • Thermistor 2
  • Analog-in-1 -Analog Widget
  • Analog-in-2
  • Analog-in-2 

| Configuration

You can see the configuration screen for the Sense has Thermistor 1 and 2, and Analog-in 1 and 2 that can be enabled or disabled.

3.png

 

| Configuration Parameters

Parameter

Purpose

Default Value

Values in the drop-down list

temperatureOffset

To set the offset temperature

0 (°F)

Range from -10 to + 10 in .1 increments  

 

TH1 

To sense inputs

 

10K Type 2 probe.

 

Generic 1-100Kohms

TH2 

To sense inputs

 

10K Type 2 probe.

 

Generic 1-100Kohms

Analog- in1

To define the inputs to sense

 Generic 0-10V

  • 0-2 in. Pressure Sensor
  • 0-0.25 Differential Pressure Sensor
  • Airflow Sensor
  • Humidity, CO2(0-2000)
  • CO(0-100)
  • NO2(0-5)
  • Current TX (0-10Amps)
  • Current TX (0-20Amps)
  • Current TX (0-50Amps)
  • ION Meter 0-1 Million ions/cc

Analog- in1

To define the inputs to sense

Generic 0-10V

  • 0-2 in. Pressure Sensor
  • 0-0.25 Differential Pressure Senso
  • Airflow Sensor
  • Humidity, CO2(0-2000)
  • CO(0-100)
  • NO2(0-5)
  • Current TX (0-10Amps)
  • Current TX (0-20Amps)
  • Current TX (0-50Amps)
  • ION Meter 0-1 Million ions/cc

You can see widgets configured in the heatmap pages below.