|How it Works
The SSE module is like a simple thermostat, works independently with no dependency on main CCU. The CCU really acts as an aggregator point, The system profile in this case is set to default and is not connected to any HVAC equipment.
The CCU at times is used for various system level profiles like the DAD/VAV/OAO. So while the CCU is in the heating mode, the SSE is connected to a split AC for cooling the room (like a server room in winter).
Based on the equipment selection the SSE is providing either heating / cooling.
Multiple SSE modules may be paired to a single zone.
The SSE module can be in setback mode based on the vacation or the unoccupied schedule, and since the SSE does not control any HVAC equipment it does not have a Zone priority.
|Wiring
|Configuration
The configuration screen displays the following
- Relay-1
- Relay-2
- Thermistor-1
- Thermistor-2
Configuration Parameters
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Relay 1 |
To enable Heating / cooling |
Cooling |
Heating Cooling |
Relay 2 |
To enable Fan |
Fan Speed |
NA |
Thermistor-1 |
To enable supply air temperature monitoring |
NA |
NA |
Thermistor-2 |
To enable external temperature sensing |
NA |
NA |