4 Minute Read
| How it Works
The 75F HyperStat Conventional Package Unit profile is a standalone profile, that provides heating and cooling equipment controls for conditioning.
The HyperStat provides the flexibility to choose between fully modulating and staged equipment control. Possible equipment configurations include:
- 3 Stages of cooling equipment control
- 3 Stages of heating equipment control
- 3 Stages of fan speed control
- Linear and Staged Fans for cooling and heating equipment control
- 2 Thermistor inputs
- Fan Enabled and Occupied Enable
Additional interlock inputs are provided for door/window/keycard sensors. Onboard sensors for CO2 and humidity provide separate damper control for DCV or humidification/dehumidification.
Sample applications include:
- Single zone staged CAV RTU for retail space.
- Single zone fully modulating VAV RTU for an industrial setting
- Split unit for a small warehouse office.
| Application of Deadband and Hysteresis
The diagrams below show the application of the Deadband and Hysteresis Band and their role:
| Wiring
| Configuration
- Select the HyperStat option from the device screen.
- Select Conventional Package Unit (CPU) from the module type.
The pairing options are displayed on the screen which provide the steps to successfully pair the device.
- Put the device in the Pairing mode.
- Select the device MAC address from the broadcasting window, or click connect manually to manually pair the device. For steps to manually pair refer to Alternate/Manual Pairing for HyperStat
- Enter the PIN displayed on the device and press Pair.
- Click Pair to start pairing the device.
You can see the configuration screen for the CPU with the following options available for configuration.
| Configuration Parameters
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Temperature Offset |
To set the offset temperature |
0 (°F) |
Range from -10 to + 10 in .1 increments |
Enable Auto Force Occupied |
To enable Auto force occupied Note: Auto Forced occupied/forced occupied and Auto-Awaycannot work together. |
Disabled
|
Enable |
Enable Auto Away |
To enable auto away Note: Auto Forced occupied/forced occupied and Auto Away cannot work together. |
Disabled
|
NA |
Relay 1 |
To enable staged conditioning |
Cooling Stage 1 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 2 |
To enable staged conditioning |
Cooling Stage 2 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 3 |
To enable staged conditioning |
Fan low speed |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 4 |
To enable staged conditioning |
Heating Stage 1 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 5 |
To enable staged conditioning |
Heating Stage 2 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low Speed Fan medium Speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 6 |
To enable staged conditioning |
Fan High Speed |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Analog out 1 |
To enable modulating heating or cooling conditioning and fan speed |
Cooling |
Cooling Linear Fan Speed Heating DCV Damper Staged Fan Speed |
Analog out 2 |
To enable modulating heating or cooling conditioning and fan speed |
Fan speed |
Cooling Linear Fan Speed Heating DCV Damper Staged Fan Speed |
Analog out 3 |
To enable modulating heating or cooling conditioning and fan speed |
Heating |
Cooling Linear Fan Speed Heating DCV Damper Staged Fan Speed |
Thermistor 1 |
To enable Airflow temperature sensor/Enable Generic Fault (NO)/Enable Generic Fault (NC) |
Disabled |
Airflow Temperature Generic Fault (NO) Generic Fault (NC)
|
Thermistor 2 |
To enable door and window sensor1/Enable Generic Fault (NO)/Enable Generic Fault (NC) |
Disabled |
Door/Window Sensor (TH2) Generic Fault (NO) Generic Fault (NC)
|
Analog in 1 |
To enable additional sensor inputs |
Key Card Sensor |
Current TX (0-10Amps) Current TX (0-20Amps) Current TX (0-50Amps) Key Card Sensor Door/Window Sensor 1 |
Analog in 2 |
To enable additional sensor inputs |
Current TX (0-20Amps) |
Current TX (0-10Amps) Current TX (0-20Amps) Current TX (0-50Amps) Key Card Sensor Door/Window Sensor 2 |
Analog-out1AtMinCooling |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 1V increments |
Analog-out1AtMaxCooling |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 1V increments |
Analog-out2AtMinFan |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 1V increments |
Analog-out2AtMaxFan |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 1V increments |
Analog-out3AtMinHeating |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 1V increments |
Analog-out3AtMaxHeating |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 1V increments |
Analog Out 2 at Fan low |
To set the damper positions at staged fan speeds |
30% |
Range from 0% to 100% in 10% increments |
Analog Out 2 at Fan medium |
To set the damper positions at staged fan speeds |
60% |
Range from 0% to 100% in 10% increments |
Analog Out 2 at Fan high |
To set the damper positions at staged fan speeds |
100% |
Range from 0% to 100% in 10% increments |
CO2 Threshold |
To set the CO2 Threshold value to control the DCV damper opening. |
800 ppm |
Disable, and range from 0 ppm to 4000 ppm in 10 ppm increments |
CO2 Target |
To set the CO2 Target value for the CCU level alerts |
1000 ppm |
Disable, and range from 0 ppm to 4000 ppm in 10 ppm increments |
VOC Threshold |
To set the VOC threshold value for the device level alerts |
10000 ppb |
Disable, and range from 0 ppb to 10000 ppb in 100 ppb increments |
VOC Target |
To set the VOC target value for the CCU level alerts |
10000 ppb |
Disable, and range from 0 ppb to 10000 ppb in 100 ppb increments |
PM 2.5 Threshold |
To set the PM 2.5 threshold value for the device level alerts |
1000 ppb |
Disable, and range from 0 ug/m³ to 1000 ug/m³ in 5 ug/m³ increments |
PM2.5 Target |
To set the VOC target value for the CCU level alerts |
1000 ppb |
Disable, and range from 0 ug/m³ to 1000 ug/m³ in 5 ug/m³ increments |
Test Signal
This is used for troubleshooting and testing the equipment if the configuration and the field setup are in sync, and the device is communicating properly with the controlled equipment. Also at any point, you can override the value of the output the algorithm decides.
We can use the test signal for relays to turn them on or for analog out to ramp up and see if the equipment works according to commands from the device.
Test Signal Time Out
once enabled it will be active for an hour if the screen is not changed, after an hour of no interaction on the screen. zone screen displays and the test signal will be OFF.
If the screen changes from the test signal configuration screen it will be timed out in one minute (time for the algorithm to run next).
Note: The test signal for modulating output is in deci volts ranging from 0.0dV to 100.0dV.
- Configure the required parameters.
Additional parameters are made available when DCV Damper or Linear/ Staged Fan Speed is one of the Analog Outputs as below.
DCV Damper
When DCV damper is selected as below:
The following additional options are made available for configuring.
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Analog Out at Min DCV Damper |
To set the minimum analog out value for modulating DCV Damper Control |
2V |
Range from 0V to 10V in 1V increments |
Analog Out at Max DCV Damper |
To set the maximum analog out values for modulating DCV Damper Control |
10V |
Range from 0V to 10V in 1V increments |
CO2 Damper Opening Rate |
To set damper opening rate based on the CO2 Thresholds |
10% |
Range from 0% to 200% in 10% increments |
| Analog Out for Fan Speeds
You can now select a Linear Fan speed or a staged fan speed control for the Analog Out 2 as below.
Linear Fan Speed as Analog Out
When linear fan speed is selected as below.
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Analog Out at Min Linear Fan Speed |
To set the minimum analog out value for modulating Linear Fan Speed Control |
2V |
Range from 0V to 10V in 1V increments |
Analog Out at Max Linear Fan Speed |
To set the maximum analog out values for modulating Linear Fan Speed Control |
10V |
Range from 0V to 10V in 1V increments |
For the Linear Fan speed selection under Analog Out 2, A tuner parameter Minfanruntimepostconditioning is also introduced, as below. This tuner defines the period for which the Last known analog out fan speed needs to be run after the conditioning is turned off.
Staged Fan Speed as Analog Out
When staged fan speed is selected as below.
The following additional options are made available for configuring.
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Fan out During Cooling Stage 1 |
To set the analog out value for fan speed during stage 1 cooling |
7V |
Range from 0V to 10V in 1V increments. |
Fan out During Cooling Stage 2 |
To set the analog out value for fan speed during stage 2 cooling |
10V |
Range from 0V to 10V in 1V increments |
Fan out During Heating Stage 1 |
To set the analog out value for fan speed during stage 1 heating |
7V |
Range from 0V to 10V in 1V increments |
Fan out During Heating Stage 2 |
To set the analog out value for fan speed during stage 1 heating |
10V |
Range from 0V to 10V in 1V increments |
Analog-Out2 at Fan Low | To set Analog out percentage values for Fan Low. | 70% | Range from 0% to 100% in 1% increments |
Analog-Out2 at Fan Medium | To set Analog out percentage values for Fan Medium. | 80% | Range from 0% to 100% in 1% increments |
Analog-Out2 at Fan High | To set Analog out percentage values for fan High. | 100% | Range from 0% to 100% in 1% increments |
Analog-Out2 at Fan Recirculate | To set Analog out values in Volt for Fan during recirculate. | 4V | Range from 0V to 10V in 1V increments |
Fan out During Heating Stage 3 |
To set the analog out value for fan speed during stage 1 heating |
10V |
Range from 0V to 10V in 1V increments |
Note: The Minfanruntimepostconditioning tuner value is also applicable for the stage fan speed selection under Analog-out 2. This tuner defines the period for which the stage 1 fan /Fan low speed needs to be run after the conditioning is turned off.
| Operation
The above options will appear based on the number of heating and cooling stages associated with the relays and if there are no heating/cooling stages then the staged fan cannot be associated with the AOs.
This means the user can now decide at exactly what speed the VFD, or analog fan should function when the cooling or heating stages are triggered, which effectively takes care of any kind of disproportionate operation between the cooling/heating stages and the analog fan.
This means now the analog fan operates at least at 75-80% of its maximum speed when the cooling/heating stage 1 is triggered.
Also when the no cooling or heating stages are triggered due to zero loop output, we can have a small amount of fan loop output, that could provide a small percentage of fan speed, managed by altering the Analog Fan speed multiplier, tuner parameter.
| IAQ Parameters Display Settings in the HyperStat Device
The profile also allows the user to set IAQ parameters that can be displayed in the HyperStat device's home screen.
Note: Only two of the IAQ parameters can be set at a time, to be displayed on the HyperStat device's home screen, or none can be enabled.
Before the parameters are enabled, the HyperStat device screen is showcased as below:
When parameters are enabled, and thresholds set as below.
The enabled parameter values and the threshold breach message are displayed on the HyperStat device's screen as below.
When parameters are enabled, and thresholds set as below.
The enabled parameter values are displayed on the HyperStat device screen along, with an alert message for a breach in any of the four IAQ parameters as below:
The configuration also provides an option to disable the targets and thresholds for the IAQ parameters CO2, VOC, and PM2.5 as below.
- Click Set to confirm the configuration changes.
| Post Configuration
The zones paired with the Conventional Package Unit (CPU) profile is displayed in the CCU as below.
You can see widgets configured in the heatmap pages in the portals as below.
You are also provided with profile reconfiguration options from the Internal portal as shown below, with all the features and capabilities that were available in CCU as explained in the above sections.
Note: Changes made to the re-configuration section are cascaded to the CCU and the HyperStat device.
| Modes & Operations
As in the other HyperStat profiles, the HPU profile as well supports the following fan and conditioning modes.
Fan Modes
- Off
- Auto
- Fan Low Current Occupied Period
- Fan Low Occupied Period
- Fan Low All Times
- Fan Medium Current Occupied Period
- Fan Medium Occupied Period
- Fan Medium All Times
- Fan High Current Occupied Period
- Fan High Occupied Period
- Fan High All Time
Based on the fan stages configured in the configuration window, the fan stages are made available in CCU and the portal for selection as user intents.
Note: The HyperStat hardware supports only the following fan modes at its end,
And when a change is made, it would translate to the following in the CCU.
- Auto------ Auto
- Low------Fan Low Current Occupied Period
- Medium-------Fan Medium Current Occupied Period
- High-------Fan High Current Occupied Period
Conditioning Modes
- Off
- Auto
- Cool Only
- Heat Only
| Controls and Triggers Strategy
Controls | Trigger Strategy | ||||||||||
Cooling Stages | Cooling stages trigger when the zone demands cooling, based on the current temperature. The cooling stages switch ON based on the cooling loop output, whose values are scaled for the different stages. And switches off based on conditioned current temperature values. | ||||||||||
Heating Stages |
Heating stages trigger when the zone demands to heat, based on the current temperature. The heating stages switch ON based on the heating loop output, whose values are scaled for the different stages. And switches off based on conditioned current temperature values. |
||||||||||
Fan Stages |
Fan stages trigger based on the fan loop output which is a result of cooling loop and heating loop outputs, during cooling and heating operation respectively. Fan control configured as modulating using analog out the percentages for the low, medium, and high are altered to 30% 60%, and 100% respectively. |
||||||||||
Fan Enable |
Fan enable is a provision introduced to enable additional fan control, which switches "ON" during the occupied schedule, and when any conditioning is happening during the unoccupied schedule. Example:
Note: Fan Enabled is not a control option for the Fan stages. the fan stages control needs to be mapped separately for the system to start conditioning.
When the Fan Enabled is configured alongside the AnalogOut-based Staged fan speeds, or staged fan speeds on other relays. The Analog Out minimum Fan, or the relay for minimum Fan speed is turned ON even when the fan loop output is <10% without considering the relay activation hysteresis. |
||||||||||
Occupied Enable | A relay mapped to Occupied Enable is "ON" whenever the zone is in an occupied schedule and "OFF" when any conditioning happens during an unoccupied schedule. | ||||||||||
Humidifier |
A Relay mapped to the humidifier is turned on whenever the humidity level for the CPU drops below the target Minimum Inside Humidity, a tuner value. And shows the user a target humidity control in Zone Screen on CCU and Facilisight portal |
||||||||||
De Humidifier |
A Relay mapped to the dehumidifier is turned on whenever the humidity level for the CPU goes above the target Minimum Inside Humidity, a tuner value. And shows the user a target humidity control in Zone Screen on CCU and Facilisight portal |
||||||||||
Demand Control Ventilation (DCV) |
The DCV control is used to control an independent damper for the ventilation of air into the zone. based on the following additional parameters set during configuration.
This allows for very granular control of the IAQ. It is driven or triggered by the DCV Loop Output which is a resultant of the above-configured parameters. Example: During an occupied time If the Zone CO2 value > zoneCO2Threshold then DCV damper control triggers based on the DCV loop output. If the Zone CO2 value < zoneCO2Threshold there will be no DCV damper trigger, and the relay will be set to OFF. |
||||||||||
Door/Window Sensing |
The door/window sensors are used to automatically override the operation of a zone, for the presence of doors and windows in the zone, Where the door/window can be opened and there can be a loss of the actual conditioning that is in effect. The Door or Window sensor can be a Thermistor Input or Analog Input.
When the door is open and the zone is occupied or unoccupied the zones operate as per the table below.
Note: If this option is enabled by the user, this affects the conditioning status of the entire zone if multiple modules are paired in the zone. |
||||||||||
Keycard Sensor |
The Keycard sensors are also used to automatically override the operation of a zone, where when the key card is removed from the keycard slot in a room/zone, which means the occupant of the room is no longer in the room leading to loss of the actual conditioning that is in effect. Up to one keycard sensor can be connected for a zone. When the Keycard sensor is a part of the Analog IN, a Voltage is detected, based on which the zone operations are overridden.
For more information on the keycard sensor working refer HyperStat Installation Note: Keycard functioning is separate from the "Auto Away" toggle. There is no interlinking between keycard-based functioning and Occupancy sensor-based functioning. |
||||||||||
Current Transformer |
Current transformer is another analog input option in the profiles for HyperStat, it connects to a transformer in the circuit and simply measures the current consumption in the circuit. For more information on the current transformers as Analog IN refer HyperStat Installation |
Note: Each module configured can have up to 2 door/window sensors, but sensor type keycard can only be one for the given equipment. If keycard is present, the zone is considered occupied by default.
| Equip Graphics for Hyperstat CPU
Equipment graphics is available for all the terminal profiles. It provides a graphical representation of system-level equipment and enables monitoring of key point parameters associated with terminal profiles, along with the alert rings and alert severity legends displayed.
The highlighted list of points is predefined for visualization alongside the graphic for the respective profile.
| Feature Availability Version
Feature | Hardware/Firmware | Version |
The fan control during recirculate, and the tuner Minfanruntimepostconditioning supports as a part of the Title 24 enhancements |
CM | 3.47 and above. |
The Staged Fan control support for Analog Out | HyperStat | 1.18 and above |
The fan control during recirculate, and the tuner Minfanruntimepostconditioning supports as a part of the Title 24 enhancements |
HyperStat | 1.26 and above |
Comments
0 comments
Please sign in to leave a comment.