6 Minute Read
| Overview
The HyperStat is part of 75F's vertically-integrated suite of intelligent building solutions, delivering multi-mode sensing, remote monitoring , and individual zone control for the comfort and productivity of building occupants, for more information refer to HyperStat Installation & HyperStat UI
The HyperStat hardware is capable to work as a dependent device configured with a 75F's CCU configured for various system-level profiles, or with any external Modbus or BACnet devices as a Modbus or BACnet slave, and it can also work as an independent or standalone device which can work as per profiles that can be configured in the HyperStat itself.
This software side support on the HyperStat device provides enhanced control of standalone equipment that is controlled and monitored by the 75F solution for both modulating and multi-staged equipment.
The feature is introduced to address the HVAC needs of the customer who would like to use the 75F's HyperStat alone for automating the HVAC operation based on certain profiles.
The profile supported for the standalone operation are.
- Conventional Package Unit (CPU)
- Heat Pump Unit (HPU)
- 2 Pipe Fan Coil Unit (2PFCU)
- 4 Pipe Fan Coil Unit (4PFCU)
| Wiring
| Setting HyperStat to Standalone
From the HyperStat home UI screen,
- Press the + and - buttons together to navigate to the other screen of the HyperStat.
The inputs UI screen is displayed.
From the inputs UI screen.
- Press the next button thrice to reach the HVAC profile screen.
- Press the down arrow button to navigate to the select profile option on the screen.
- Press the select button to access the desired profile.
- Press the down arrow button to select the Conventional Package Unit (CPU) profile from the list available.
- Press the back button to confirm setting HyperStat as standalone, select Conventional Package Unit (CPU) as profile, and return to the HVAC profile screen.
| Configuring Standalone Conventional Package Unit (CPU)
- Press the down arrow button once to navigate to the Configure profile option.
- Press select to access the Configure profile option which opens the configuration options available for the Conventional Package Unit (CPU) profile. It should be noted that all the selections viewed are set to default CPU relay and analog out mapping.
- Press the down arrow to navigate to the configuration parameter under the Conventional Package Unit (CPU) profile
- Press the select button to access the parameters options available under the different configurable relays, analogs, and other available options.
- Press the down and up arrows to locate the required parameter to set for the relays, analogs, and other available options.
- Press the deselect button to confirm the selection.
- Repeat the above step to navigate, access, and select different parameter options for all the available relays, analogs, and others, till the desired configuration settings are met.
- Refer to the Configuration Parameter table below for the parameter options available under different relays, analogs, and others and their purpose to help in the configuration.
| Configuration Parameters
Parameter |
Purpose |
Default Value |
Values in the drop-down list |
Temperature Offset |
To set the offset temperature |
0 (°F) |
Range from -10 to + 10 in .1 increments |
Enable Auto Force Occupied |
To enable Auto force occupied |
Disabled
|
NA |
Enable Auto Away |
To enable auto away
|
Disabled
|
NA |
Relay 1 |
To enable staged conditioning |
Cooling Stage 1 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 2 |
To enable staged conditioning |
Cooling Stage 2 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 3 |
To enable staged conditioning |
Fan low speed |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 4 |
To enable staged conditioning |
Heating Stage 1 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 5 |
To enable staged conditioning |
Heating Stage 2 |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan Low Speed Fan medium Speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Relay 6 |
To enable staged conditioning |
Fan High Speed |
Cooling Stage1 Cooling Stage2 Cooling Stage3 Heating Stage1 Heating Stage2 Heating Stage3 Fan low speed Fan medium speed Fan highspeed Fan Enable Occupied Enable Humidifier Dehumidifier |
Analog out 1 |
To enable modulating heating or cooling conditioning and fan speed |
Cooling |
Cooling Fan Speed Heating DCV Damper |
Analog out 2 |
To enable modulating heating or cooling conditioning and fan speed |
Fan speed |
Cooling Fan Speed Heating DCV Damper |
Analog out 3 |
To enable modulating heating or cooling conditioning and fan speed |
Heating |
Cooling Fan Speed Heating DCV Damper |
Thermistor 1 |
To enable Airflow temperature sensor |
Disabled |
NA |
Thermistor 2 |
To enable door and window sensor1 |
Disabled |
NA |
Analog in 1 |
To enable additional sensor inputs |
Key Card Sensor |
Current TX (0-10Amps) Current TX (0-20Amps) Current TX (0-50Amps) Key Card Sensor Door/Window Sensor 2) |
Analog in 2 |
To enable additional sensor inputs |
Current TX (0-20Amps) |
Sensor Current TX (0-10Amps) Current TX (0-20Amps) Current TX (0-50Amps) Key Card Sensor Door/Window Sensor 2) |
Analog-out1AtMinCooling |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 2V increments |
Analog-out1AtMaxCooling |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 2V increments |
Analog-out2AtMinFan |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 2V increments |
Analog-out2AtMaxFan |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 2V increments |
Analog-out3AtMinHeating |
To set the analog out values for modulating conditioning controls |
2V |
Range from 0V to 10V in 2V increments |
Analog-out3AtMaxHeating |
To set the analog out values for modulating conditioning controls |
10V |
Range from 10V to 0V in 2V increments |
Analog Out 2 at Fan low |
To set the damper positions at staged fan speeds |
30% |
Range from 0% to 100% in 10% increments |
Analog Out 2 at Fan medium |
To set the damper positions at staged fan speeds |
60% |
Range from 0% to 100% in 10% increments |
Analog Out 2 at Fan high |
To set the damper positions at staged fan speeds |
100% |
Range from 0% to 100% in 10% increments |