| Overview

The HyperStat is part of 75F's vertically-integrated suite of intelligent building solutions, delivering multi-mode sensing, remote monitoring , and individual zone control for the comfort and productivity of building occupants, for more information refer to HyperStat Installation & HyperStat UI

The HyperStat hardware is capable to work as a dependent device configured with a 75F's CCU configured for various system-level profiles, or with any external Modbus or BACnet devices as a Modbus or BACnet slave, and it can also work as an independent or standalone device which can work as per profiles that can be configured in the HyperStat itself.

This software side support on the HyperStat device provides enhanced control of standalone equipment that is controlled and monitored by the 75F solution for both modulating and multi-staged equipment.

The feature is introduced to address the HVAC needs of the customer who would like to use the 75F's HyperStat alone for automating the HVAC operation based on certain profiles.

The profile supported for the standalone operation are.

  • Conventional Package Unit (CPU)
  • Heat Pump Unit (HPU)
  • 2 Pipe Fan Coil Unit (2PFCU)
  • 4 Pipe Fan Coil Unit (4PFCU)

| Wiring

CPU.png

| Setting HyperStat to Standalone

From the HyperStat home UI screen,

mceclip1.png

  • Press the + and -  buttons together to navigate to the other screen of the HyperStat.

The inputs UI screen is displayed.

mceclip2.png

From the inputs UI screen.

  • Press the next button thrice to reach the HVAC profile screen.

mceclip3.png

  • Press the down arrow  mceclip1.png   button to navigate to the select profile option on the screen.

mceclip5.png

  • Press the select button to access the desired profile.

mceclip1.png

  • Press the down arrow  mceclip2.png   button to select the Conventional Package Unit (CPU) profile from the list available.

mceclip0.png

  • Press the back button to confirm setting HyperStat as standalone, select Conventional Package Unit (CPU) as profile, and return to the HVAC profile screen.

| Configuring Standalone Conventional Package Unit (CPU) 

mceclip2.png

  • Press the down arrow button once to navigate to the Configure profile option.

mceclip3.png

  • Press select to access the Configure profile option which opens the configuration options available for the Conventional Package Unit (CPU) profile. It should be noted that all the selections viewed are set to default CPU relay and analog out mapping.

mceclip4.png

  • Press the down arrow to navigate to the configuration parameter under the Conventional Package Unit (CPU) profile

mceclip0.png

  • Press the select button to access the parameters options available under the different configurable relays, analogs, and other available options.

mceclip1.png

  • Press the down and up arrows to locate the required parameter to set for the relays, analogs, and other available options.

mceclip2.png

  • Press the deselect button to confirm the selection.

mceclip3.png

  • Repeat the above step to navigate, access, and select different parameter options for all the available relays, analogs, and others, till the desired configuration settings are met.
  • Refer to the Configuration Parameter table below for the parameter options available under different relays, analogs, and others and their purpose to help in the configuration.

mceclip4.png

mceclip5.png

mceclip6.png

| Configuration Parameters

Parameter

Purpose

Default Value

Values in the drop-down list

Temperature Offset

To set the offset temperature

0 (°F)

Range from -10 to + 10 in .1 increments  

Enable Auto Force Occupied

To enable Auto force occupied

Disabled

 

NA

Enable Auto Away

To enable auto away

 

Disabled

 

NA

Relay 1

To enable staged conditioning

Cooling Stage 1 

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Relay 2

 

To enable staged conditioning

Cooling Stage 2  

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Relay 3

To enable staged conditioning

Fan low speed

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Relay 4

To enable staged conditioning

Heating Stage 1

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Relay 5

To enable staged conditioning

Heating Stage 2

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan Low Speed

Fan medium Speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Relay 6

To enable staged conditioning 

Fan High Speed 

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Analog out 1

To enable modulating heating or cooling conditioning and fan speed

Cooling

Cooling

Fan Speed

Heating

DCV Damper

Analog out 2

To enable modulating heating or cooling conditioning and fan speed

Fan speed

Cooling

Fan Speed

Heating

DCV Damper

Analog out 3

To enable modulating heating or cooling conditioning and fan speed

Heating

Cooling

Fan Speed

Heating

DCV Damper

Thermistor 1

To enable Airflow temperature sensor

Disabled

NA

Thermistor 2

To enable door and window sensor1

Disabled

NA

Analog in 1

To enable additional sensor inputs

Key Card Sensor 

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 2)

Analog in 2

To enable additional sensor inputs

Current TX (0-20Amps) 

Sensor 

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 2)

Analog-out1AtMinCooling

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog-out1AtMaxCooling

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 

 

Analog-out2AtMinFan

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog-out2AtMaxFan

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 

Analog-out3AtMinHeating 

To set the analog out values for modulating conditioning controls

2V

Range from 0V to 10V in 2V increments  

Analog-out3AtMaxHeating

To set the analog out values for modulating conditioning controls

10V

Range from 10V to 0V in 2V increments 

Analog Out 2 at Fan low

To set the damper positions at staged fan speeds

30%

Range from 0% to 100% in 10% increments 

Analog Out 2 at Fan medium

To set the damper positions at staged fan speeds

60%

Range from 0% to 100% in 10% increments 

Analog Out 2 at Fan high

To set the damper positions at staged fan speeds

100%

Range from 0% to 100% in 10% increments 

 

 

 