| SETUP & CONFIGURATION
| Registration:
- Welcome Screen: press “Get Started” in bottom right corner.
- Select the wireless network from the list and enter the password. If you are connecting to a hidden network, select the “+” in the upper right corner, and enter the SSID and password. “Connected” will be displayed below the selected network. Select the right arrow to continue.
- Select Registration Type.
-
- Standard Install – Use this option if you are registering the first tablet in a new building
- Add CCU to existing building – Use this option if you are registering a tablet in a building that has one or more tablets already associated with it.
- Pre-Configured – Use this option if you have a six-digit configuration code provided by 75F.
- Replace Existing CCU – Use this option if the existing tablet in an already installed building is damaged and needs to be replaced.
Select the right arrow to continue.
- Account Setup – Standard Install
- Email: enter the email of the Facility Manager
- Installer Email Address: enter the email of the lead installer
- CCU Name: Enter a unique identifier for the CCU and the equipment it controls (e.g. West Wing, RTU 4, Exterior offices)
- Building Name: Enter the name of the building
- Address: Enter the street address of the building
Once complete, select “Register.” If this is the first building associated with the Facility Manager’s email address, they will be sent an email with a password. Otherwise, the password must be provided. Once registered, select the right arrow to continue.
- Product Options: select all options that will be installed in this system. 75F can edit these options. Select the right arrow to continue.
- Installer Options
- Pairing Start Address: Drop-down menu specifying the start address for components paired to this CCU. You should not need to change this option. The unique identifiers will be assigned to modules in increasing order from this #. (e.g. 9003, 9 is the channel the mesh network will communicate on, 003 is the unique identifier assigned for that device on channel 9)
Note: Pairing addresses range from 1000 to 10900.
The System integrator will have to know what RF frequencies are permissible in the country where it is installed and use only those
- Use Outside Temperature Lockout: Selecting this allows the user to prevent the use of either Cooling or Heating modes based on the Outdoor Temperature.
- Temperature Limits: Set your user limits for both heating and cooling. Also set your building limits here.
Select the right arrow to continue.
- Security: this page allows you to set up passwords to access Settings and/ or Setup. This can be accessed and changed later. It is recommended to skip this for now, as configuration will take less time without it. Select the right arrow to continue.
- System Profile: Select the type of system on which the CCU is being installed.
Select the right arrow to continue.
- Floor Plan and Configuration: Setup floors, rooms, and pairings. To pair devices follow the pairing instructions on the Installation guide of the device you are pairing.
- System Settings: Change settings operational system settings.
- Conditioning Mode: Set the mode of the system. “Auto” will allow the system to decide to heat or cool.
- Use DX for Overnight Dehumidification: When humidity is high mechanical cooling will run during unoccupied hours to reduce the indoor humidity level.
- Compensate for Humidity: selecting this option will control the space temperature based on the total enthalpy of the air instead of just the dry-bulb temperature. For example, in very humid situations, the system will cool the space below the setpoint. This will make it so it “feels like” the desired setpoint.
- Stage 1 Fan Always ON: selecting this option will run stage 1 fan even during unoccupied times.
- Schedule
- Drop-down Menu: Allows for selection of System Schedule (editable locally) or a Named Schedule (editable from Facilisight)
- Pencil Symbol: Click to edit system schedule
- Status: Displays the System Status
- Vacation: Set vacation days where the system can operate in setback to save energy.
Select the right arrow to continue.
- CONGRATULATIONS! You have finished configuring the CCU. You may review your selections on this page. Press the left arrow to make changes, or press finish if you are satisfied.