| Overview
This check verifies the zone humidity sensor quality on your SmartNodes and HyperStats.
| When it passes
A PASS means your zones humidity sensors are working correctly and reading within acceptable ranges.
| When it fails
A FAIL means the zone’s humidity sensor data was not reading correctly. It was either out of acceptable humidity range or showed abnormal data when compared to the other zones. For example, in the example below, the humidity sensors were all reading too low:
| Common causes
This typically occurs due to one of two reasons:
- Bad wiring: The connectors may have loosened or the wires may not have been spliced correctly.
- Broken sensor: The sensor may be defective.
| Next Steps
- Verify sensor wiring. The connections may not have seated correctly.
- Was the failure observed in one zone or many zones? Are other sensors for the zone (e.g. temp sensor) reading correctly? Failures across multiple zones would indicate unexpected environmental conditions.
- If the wiring is correct, you may need to replace the sensor.