- Check incoming 24vac power at your Smart Node device. Verify that there are no safeties or relays that could interrupt power to the Smart Node.
- If 23 volts and under convert to a larger VA power supply
- Check your 24vac and C connections at your Smart Node device
- Be sure to check for any temporary drops in voltage when both relays close.