| Overview
This check verifies the zone damper operation in multi-zone configurations. This is achieved by modulating the zone dampers while conditioning the zones, and inspecting the discharge-air and zone-temp responses.
This check will be SKIPPED if the outside-air temperature is below 50°F and no heating equipment is installed.
| When it passes
A PASS means your zone dampers are wired correctly and adequately modulating airflow to the zones.
| When it fails
A FAIL means the dampers are not providing adequate airflow to the zones.
| Common causes
This typically occurs due to one of two reasons:
- Dampers are operating in reverse of what is configured
- Zones are not served by the correct system equip (ductwork is different than pairing)
| Next Steps
- Verify damper operation using manual output from the node.
- Verify duct layout.