| Overview
This check verifies the cooling capability of the standalone cooling equipment.
This check will be SKIPPED if any of the following is true:
- The outdoor-air temps are too low (below 50F): this ensures we do not freeze out the ducts
- The unit is configured for Heating Only
| When it passes
A PASS means the cooling unit is working as expected, and adequately conditioned the zone being served.
| When it fails
A FAIL means the unit did not respond to the cooling commands or adequately cool the zone.
| Common causes
The cooling unit is not working correctly due to incorrect wiring or bad sensor placement.
| Next Steps
- Verify cooling equipment operation using manual output from the node or stat.
- Verify sensor placement and ductwork layout if some zones are not reporting data consistent with others.