| Overview

Once the HyperStat is wired and configured as a BACnet server, it would start exposing a number of points for a BACnet BMS to start subscribing. and using the points in the BMS.

The points are exposed over the MSTP (Master-Slave/Token Passing) protocol.

| Generic Points Exposed

The table below talks about the points exposed by HyperStat, their descriptions, the object type they belong to, and their multistate if applicable.

Points ExposedDescriptionObject TypeMultistate Values/Inputs/Enums
DeviceEntity that exposes the HyperStat equipmentDeviceNA
HyperStat Network PortEntity that exposes the network the device is connected toNetworkNA
Room TemperatureEntity that exposes the current temperature sensed by the onboard temperature sensor in the device.Analog InputNA
CO2Entity that exposes the CO2 levels sensed by the onboard CO2 sensor in the device.Analog InputNA
UVIEntity that exposes the Ultraviolet Intensity sensed by the onboard UV sensor in the device.Analog InputNA
HumidityEntity that exposes the current humidity sensed by the onboard humidity sensor in the deviceAnalog InputNA
IlluminanceEntity that exposes the Illuminance levels sensed by the onboard Illuminance sensor in the device.Analog InputNA
Analog Input 1Entity that exposes the scaled voltage value, for the parameter configured for Analog Input 1 during the profile configuration.Analog InputNA
Analog Input 2Entity that exposes the scaled voltage value, for the parameter configured for Analog Input 2 during the profile configuration.Analog InputNA
Thermistor 2Entity that exposes the scaled ohms value, for the parameter configured for Thermistor 2 during the profile configuration.Analog InputNA
Analog Out 2Entity that exposes the scaled voltage value, for the parameter configured for Analog Out 2 during the profile configuration.Analog InputNA
Active Set Temperature Heating

Entity that exposes desired temperature set for the device, for single set point style operation.

The temperature is updated when the change is made from both the Onboard Device and the BMS - BACnet client.

Analog InputNA
Thermistor 1Entity that exposes the scaled ohms value, for the parameter configured for Thermistor 1 during the profile configuration.Analog InputNA
Analog Out 1Entity that exposes the scaled voltage value, for the parameter configured for Analog Out 1 during the profile configuration.Analog InputNA
Analog Out 3Entity that exposes the scaled voltage value, for the parameter configured for Analog Out 3 during the profile configuration.Analog InputNA
Active Set Temperature Cooling

Entity that exposes desired temperature set for the device, for single set point style operation.

The temperature is updated when the change is made from both the Onboard Device and the BMS - BACnet client.

Analog InputNA
Desired Set Temperature Heating

Entity that exposes desired heating temperature set for the device, the default is 68F

The temperature is updated only when the change is made from BMS - BACnet client, not from the Device

Analog ValueNA
Max Set Temperature HeatingEntity that exposes maximum value for the desired heating temperature that can be set.Analog ValueNA
Max Set Temperature CoolingEntity that exposes maximum value for the desired cooling temperature that can be set.Analog ValueNA
Temperature OffsetEntity that exposes temperature offset values that can set during the configuration.Analog ValueNA
Desired Set Temperature Cooling

Entity that exposes desired heating temperature set for the device, the default is 72F

The temperature is updated only when the change is made from BMS - BACnet client, not from the Device

Analog ValueNA
Min Set Temperature HeatingEntity that exposes minimum value for the desired heating temperature that can be set.Analog ValueNA
Min Set Temperature CoolingEntity that exposes minimum value for the desired cooling temperature that can be set.Analog ValueNA
Heating DeadbandEntity that exposes heating deadband value applicable for the device, the default is 2FAnalog ValueNA
Max Humidity SetpointEntity that exposes the maximum humidity that can be set for the device.Analog ValueNA
Analog Out 1 Min SettingEntity that exposes the minimum scaled voltage value set for the parameter configured for Analog Out 1.Analog ValueNA
Analog Out 2 Min SettingEntity that exposes the minimum scaled voltage value set for the parameter configured for Analog Out 2.Analog ValueNA
Analog Out 2 Max SettingEntity that exposes the maximum scaled voltage value set for the parameter configured for Analog Out 2.Analog ValueNA
Occupancy StatusEntity that exposes a binary value for the occupancy statusBinary Input

0 - Unoccupied

1 - Occupied

Relay 2Entity exposed to visualize the relay 2 status.Binary Input

0 - Off

1 - On

Relay 4Entity exposed to visualize the relay 4 status.Binary Input

0 - Off

1 - On

Relay 6Entity exposed to visualize the relay 6 status.Binary Input

0 - Off

1 - On

Relay 1Entity exposed to visualize the relay 1 status.Binary Input

0 - Off

1 - On

Relay 3Entity exposed to visualize the relay 3 status.Binary Input

0 - Off

1 - On

Relay 5Entity exposed to visualize the relay 5 status.Binary Input

0 - Off

1 - On

Relay 1 EnableEntity that exposes a binary value for the relay 1 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Relay 3 EnableEntity that exposes a binary value for the relay 3 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Relay 5 EnableEntity that exposes a binary value for the relay 5 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog In 1 EnableEntity that exposes a binary value for the Analog In 1 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog Out 1 EnableEntity that exposes a binary value for the Analog Out 1 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Relay 2 Enable Entity that exposes a binary value for the relay 2 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Relay 4 Enable Entity that exposes a binary value for the relay 4 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Relay 6 Enable Entity that exposes a binary value for the relay 6 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog In 2 EnableEntity that exposes a binary value for the Analog In 2 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog Out 2 EnableEntity that exposes a binary value for the Analog Out 2 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog Out 3 EnableEntity that exposes a binary value for the Analog Out 3 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog Out 2 Pulse EnableEntity that exposes test signal enablement for the Analog Out2 Binary ValueNA
Thermistor 1 EnableEntity that exposes a binary value for the Thermistor 1 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Use TH1 As Room Temp SensorEntity that exposes whether the TH1 is connected to a room temp sensor.Binary ValueNA
Enable Auto AwayEntity that exposes a binary value for the Auto Away mode enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Analog Out 1 Pulse EnableEntity that exposes test signal enablement for the Analog Out1 Binary ValueNA
Analog Out 3 Pulse EnableEntity that exposes test signal enablement for the Analog Out3 Binary ValueNA
Thermistor 2 EnableEntity that exposes a binary value for the Thermistor 2 enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Enable Force OccupiedEntity that exposes a binary value for the Force occupied mode enabled or disabledBinary Value

0 - Disabled

1 - Enabled

Unoccupied ModeEntity that exposes a binary value when the space is unoccupied.Binary Value

0 - False

1 - True

Show CentigradeEntity that exposes a binary value for switching the temperature unit from Fahrenheit to Centigrade.Binary Value

0 - False

1 - True

Display HumidityEntity that exposes a binary value for, whether the Humidity value display is enabled or disabled at the home screen UI of the deviceBinary Value

0 - Disabled

1 - Enabled

Display CO2Entity that exposes a binary value for, whether the CO2 levels display is enabled or disabled at the home screen UI of the deviceBinary Value

0 - Disabled

1 - Enabled

Display VOCEntity that exposes a binary value for, whether the VOC levels display is enabled or disabled at the home screen UI of the deviceBinary Value

0 - Disabled

1 - Enabled

Operating ModeEntity exposes the operating mode the device or space is in Multi State InputOFF
HEATING
COOLING
Active Fan Speed

Entity exposes the fan speed mode at which the fan is currently operating.

The fan speed is updated when the change is made from both the Onboard Device and the BMS - BACnet client.

Multi State InputAUTO
LOW
MEDIUM
HIGH
Active Conditioning Mode

Entity exposes the conditioning mode at which the system is currently operating

The mode is updated when the change is made from both the Onboard Device and the BMS - BACnet client.

Multi State InputOFF
AUTO
HEAT
COOL
Occupancy StatusEntity exposes the occupancy state in which the space is currently in.Multi State InputINITIALIZING
OCCUPIED
UNOCCUPIED
OCC. AUTO AWAY
UNOCC. FORCE OCC.
Desired Conditioning Mode

Entity exposes desired conditioning mode that is available for the user to define.

The mode is updated only when the change is made from BMS - BACnet client, not from the Device.

Multi State ValueOFF
AUTO
HEAT
COOL
Temperature ModeEntity exposes temperature modes that is available for the user to define.Multi State ValueSINGLE SETPOINT
DUAL SETPOINT FIX DB
DUAL SETPOINT VAR DB
Desired Fan Speed

Entity exposes types of fan speeds that is available for the user to define.

The fan speed is updated only when the change is made from BMS - BACnet client, not from the Device

Multi State ValueOFF
AUTO
LOW
MEDIUM
HIGH
ProfileEntity exposes profiles that is available for the user to select.Multi State Value

NONE

Conventional Package Unit (CPU)

Heat Pump Unit (HPU)

2 Pipe Fan Coil Unit (2PFCU)

4 Pipe Fan Coil Unit (4PFCU)

SENSE

 

| Generic Points Exposed

The table below talks about the tuner points exposed by HyperStat, their descriptions, the object type they belong to, and their default, min max values.

Points ExposedDescriptionObject TypeDefault Value, Min, Max
VOC Alert ThresholdTuner Entity value exposed for the VOC level that is set, when VOC level exceed this value, an alert is triggered.Analog Value400, 0, 1000
Zone CO2 Damper Opening RateTuner Entity that exposes the value that determines the rate at which outside air damper will open to manage CO2 level based on return air CO2 level.Analog Value10, 0, 200
Zone CO2 TargetTuner Entity value exposed that determines target value of CO2 in a zoneAnalog Value1000, 0, 2000
Proportional Constant Tuner Entity value exposed, that produces an output action that is proportional to the deviation between the set point and the measured process value for a PI LoopAnalog Value0.5, 0.1, 1.0
Proportional Temperature Range Tuner Entity value exposed, that defines the band of temperature, or range of temperature, over which the output of the controller is proportional. Example controlling the damper operations.Analog Value2, 0, 10
Unoccupied SetbackTuner Entity value exposed, that Determines how many degrees from the desired temperature the zone will be allowed to drift during unoccupied times.Analog Value5, 0, 20
Relay Activation HysteresisTuner Entity value exposed, that determines a condition at which the relay will turn off after being turned on to control based on load.Analog Value10, 0, 100
Integral Constant Tuner Entity value exposed, with which the controller output is proportional to the amount of time the error is present.Analog Value0.5, 0.1, 1.0
Integration TimeTuner Entity value exposed that defines the amount of time the PI loop in the system integrates the error over a period until error value reaches zero. It limits the speed of response and affects the stability of the system.Analog Value30, 1, 60
Heating Deadband MultiplierTuner Entity value exposed, that manages the value of heatingdeadband. This tuner multiplies with the value of heating deadband and manages the value of heating deadbandAnalog Value0.5, 0, 5.0
Fan Speed MultiplierTuner Entity value exposed, that determines how fast a fan can move based on heating or cooling load.Analog Value1, 0.1, 3.0
Humidity HysteresisTuner Entity value exposed, that determines a condition at which humidifier/dehumidifier will turn off after being turned on to control inside humidity.Analog Value5, 1, 100
Auto Away TimeTuner Entity value exposed, During Occupied period of the zone (Not during preconditioning period), If an Occupant is not detected for this tuner duration, the zone should enter 'Auto Away' mode if occupancy is enabled.Analog Value60, 40, 300
Forced Occupied TimeEntity that exposes a time set, that determines the time for which if no occupancy is detected the zone enters autoaway mode.Analog Value120, 30, 300
Auto Away Setback TemperatureTuner Entity value exposed, that determines how many degrees from the desired temperature the zone will be allowed to drift during Auto away. zone may have different desired temperatures leading to different setbacks. Analog Value2, 0, 20

 

| Profile Specific Points Exposed

The Relay and Analog In & Out points exposed for the BACnet, and their corresponding multistate values, differ based on the profile selected for the HyperStat device.

The Tables below illustrate the different multi-state values that are exposed for the Relays, Analog Ins & Analog Outs, for the different profiles selected.

CPU (Conventional Package Unit)

The Table below is for a HyperStat configured for a Conventional Package Unit (CPU) profile.

Points ExposedDescriptionObject TypeMultistate Values/Inputs/Enums
Relay 1/2/3/4/5/6 MappingEntity exposes mappings available under Relay 1/2/3/4/5/6, for the user to select from.Multi State Value

Cooling Stage1

Cooling Stage2

Cooling Stage3

Heating Stage1

Heating Stage2

Heating Stage3

Fan low speed

Fan medium speed

Fan highspeed

Fan Enable

Occupied Enable

Humidifier

Dehumidifier

Analog In 1/2 MappingEntity exposes mappings available under Analog In 1/2, for the user to select from.Multi State Value

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 1/2

Analog Out 1/2/3 MappingEntity exposes mappings available under Analog Out 1/2/3, for the user to select from.Multi State Value

Cooling

Fan Speed

Heating

DCV Damper

 

2PIPE FCU(Fan Coil Unit)

The Table below is for a HyperStat configured for a 2PIPE FCU profile.

Points ExposedDescriptionObject TypeMultistate Values/Inputs/Enums
Relay 1/2/3/4/5/6 MappingEntity exposes mappings available under Relay 1/2/3/4/5/6, for the user to select from.Multi State Value

Auxiliary Heating Stage 1

Auxiliary Heating Stage 2

Water Valve

Fan Enabled

Occupied Enabled

Fan Low Speed

Fan Medium Speed

Fan High Speed

Humidifier

Dehumidifier

Analog In 1/2 MappingEntity exposes mappings available under Analog In 1/2, for the user to select from.Multi State Value

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 1/2

Analog Out 1/2/3 MappingEntity exposes mappings available under Analog Out 1, for the user to select from.Multi State Value

Water Modulating Valve

Fan Speed

DCV Damper

 

4PIPE FCU(Fan Coil Unit)

The Table below is for a HyperStat configured for a 4PIPE FCU profile.

Points ExposedDescriptionObject TypeMultistate Values/Inputs/Enums
Relay 1/2/3/4/5/6 MappingEntity exposes mappings available under Relay 1/2/3/4/5/6, for the user to select from.Multi State Value

Auxiliary Heating Stage 1

Auxiliary Heating Stage 2

Water Valve

Fan Enabled

Occupied Enabled

Fan Low Speed

Fan Medium Speed

Fan High Speed

Humidifier

Dehumidifier

Analog In 1/2 MappingEntity exposes mappings available under Analog In 1/2, for the user to select from.Multi State Value

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 1/2

Analog Out 1/2/3 MappingEntity exposes mappings available under Analog Out 1/2/3, for the user to select from.Multi State Value

Water Modulating Valve

Fan Speed

DCV Damper

 

Fancoil Tuner Points Exposed

For Fancoil type profiles it's not just the Relay and Analog ins and Outs that vary, additional tuner parameters are also exposed, as below.

 

Points ExposedDescriptionObject TypeDefault Value, Min, Max
FCU Aux Heating 1 ActivateTuner Entity value exposed 2Pipe FCU, that determines at what temperature, less than the heating desired temperature, should the Auxillary heating stage1 trigger.Analog Value3, 0, 10
FCU Aux Heating 2 ActivateTuner Entity value exposed 2Pipe FCU, that determines at what temperature, less than the heating desired temperature, should the Auxillary heating stage2 trigger.Analog Value3, 0, 10
FCU Two Pipe Cooling ThresholdTuner Entity value exposed for a 2 Pipe FCU, that determines if the central plant is providing cold water when compared to supply water temp sensor. If Th2 (supply water sensor) is less than 2pipeFancoilCoolingThreshold (65) then the central plant is providing cold waterAnalog Value65, 35, 70
FCU Two Pipe Heating ThresholdTuner Entity value exposed for a 2 Pipe FCU, that determines if the central plant is providing hot water when compared to supply water temp sensor. If Th2 (supply water sensor) is greater than 2pipeFancoilCoolingThreshold (85) then the central plant is providing cold waterAnalog Value85, 80, 150
FCU Water Valve Sampling on TimeTuner Entity value exposed for a 2 Pipe FCU, that defines a time interval for which the water valve needs to be opened post the waterValveSamplingWaitTime (m), before starting to sample for thresholds, when the water temperature is above or below the thresholds.Analog Value2, 0, 150
FCU Water Valve Sampling During Loop Deadband On TimeTuner Entity value exposed for a 2 Pipe FCU, that defines a time interval for which the water valve needs to be opened post the waterValveSamplingDuringLoopDeadbandWaitTime(m), before starting to sample for thresholds, when the water temperature is within the thresholds, Analog Value2, 0, 150
FCU Water Valve Wait Sampling TimeTuner Entity value exposed for a 2 Pipe FCU, that defines a time interval, if the water valve is not opened for more than this time interval, the water valve should be opened for 100% before starting to sample for threshold, when the water temperature is above or below the thresholds, this tuner Analog Value58, 0, 150
FCU Wate Valve Sampling During Loop Deadband Wait TimeTuner Entity value exposed for a 2 Pipe FCU, defines a time interval. and if the water valve is not opened for more than this time interval, the water valve should be opened for 100% before starting to sample for thresholds, when the water temperature is within the thresholds,Analog Value5, 0, 150

 

HPU (Heat Pump Unit)

The Table below is for a HyperStat configured for a HPU profile.

Points ExposedDescriptionObject TypeMultistate Values/Inputs/Enums
Relay 1/2/3/4/5/6 MappingEntity exposes mappings available under Relay 1/2/3/4/5/6, for the user to select from.Multi State Value

Compressor Stage 1

Compressor Stage 2

Compressor Stage 3

Aux Heating Stage 1

Aux Heating Stage 2

Fan Low Speed

Fan Medium Speed

Fan High Speed

Fan Enabled

Occupied Enabled

Humidifier

Dehumidifier

Change Over O Cooling

Change Over B Heating

Analog In 1/2 MappingEntity exposes mappings available under Analog In 1/2, for the user to select from.Multi State Value

Current TX (0-10Amps)

Current TX (0-20Amps)

Current TX (0-50Amps)

Key Card Sensor

Door/Window Sensor 1

Analog Out 1/2/3 MappingEntity exposes mappings available under Analog Out 1/2/3, for the user to select from.Multi State Value

Compressor Speed

Fan Speed

DCV Damper