24VAC Power Wire:
- 18 AWG, 2 conductor Non-Shielded Plenum Rated, Solid Copper Conductors
- Red/White conductors
- Red (24V), White (C)
DC Power:
- 18 AWG, 2 conductor Non-Shielded Plenum, Solid Copper Conductors
- Black/White conductors
- White (DC Power), Black (C)
Control Signal:
- 2 Conductor Shielded Plenum Rated
- Solid conductor when cabling to SmartNodes
- Stranded conductor in all other cases
- 18/2 (Wet Contacts): Red (Power), Black (C)
- 18/2: White (+), Black (-)
- 18/3: Red (Power), White (+), Black (-)
- 18/4: Red (Power), White (+), Black (- or C), Green (Misc. Signal)
Note: Recommended to only use 18/4 where there is a miscellaneous signal (ex., damper actuator feedback). Installing 18/4 for two different sensors/signals is not recommended.
Note: Use red conductor for all conductors carrying AC Power
Thermostat Cable:
- Minimum 18/8
- Shielded Plenum rated
- Refer to 75F CDDs for proper terminations per application
- User appropriately sized terminal connectors
- Ferrule connectors for push-in terminals
- Female slip-on connectors
- Fork connectors for screw-down terminals
Comments
0 comments
Please sign in to leave a comment.