browse

24VAC Power Wire:

  • 18 AWG, 2 conductor Non-Shielded Plenum Rated, Solid Copper Conductors
  • Red/White conductors
  • Red (24V), White (C)

DC Power:

  • 18 AWG, 2 conductor Non-Shielded Plenum, Solid Copper Conductors
  • Black/White conductors
  • White (DC Power), Black (C)

Control Signal:

  • 2 Conductor Shielded Plenum Rated
    • Solid conductor when cabling to SmartNodes
    • Stranded conductor in all other cases
  • 18/2 (Wet Contacts): Red (Power), Black (C)
  • 18/2: White (+), Black (-)
  • 18/3: Red (Power), White (+), Black (-)
  • 18/4: Red (Power), White (+), Black (- or C), Green (Misc. Signal)

Note: Recommended to only use 18/4 where there is a miscellaneous signal (ex., damper actuator feedback).  Installing 18/4 for two different sensors/signals is not recommended.

Note: Use red conductor for all conductors carrying AC Power

Thermostat Cable:

  • Minimum 18/8
  • Shielded Plenum rated
  • Refer to 75F CDDs for proper terminations per application
  • User appropriately sized terminal connectors
    • Ferrule connectors for push-in terminals
    • Female slip-on connectors
    • Fork connectors for screw-down terminals
Previous
Next

Comments

0 comments

Please sign in to leave a comment.

Was this article helpful?

0 out of 0 found this helpful
Powered by Zendesk