3 Minute Read
| How it Works
The VAV Fully Modulating AHU System profile uses advanced sequences that are fully outlined in ASHRAE GPC 36. For a comprehensive understanding of how GPC 36 works, please read the document in full. Here we will discuss some basic field level understanding for a quick and dirty understanding of what should be expected.
Cooling Mode - The system will call for cooling when there are enough requests for it. The AHU will maintain a SAT which is reset based on OAT. So in the fully modulating profile the AO1 will modulate up and down to maintain the cooling SAT that is set by the # of requests.
Heating Mode - The system will only go into heating mode if all zones are requiring heating. This will typically be during the morning warm up or after any major setpoint changes. When the unit needs heating AO3 will scale up due to the load and follow the heating sequences as if it were a Fully Modulating DAB unit.
Recirculation Mode -AO2 will modulate up and down to maintain the static duct pressure setpoint based on the number of requests received from the zones.
For the basics on Trim and Respond logic, please reference either GPC36 or our outline here: Trim and Respond Overview
| Wiring
| Configuration
| Configuration Parameters
| Parameters | Purpose | Default Value | Value in the Dropdown |
| Analog Out 1 | To enable modulating cooling conditioning | Cooling |
Fan Speed Compressor Speed Outside Air Damper Cooling Heating |
| Analog Out 2 | To enable modulating fan speed | Fan Speed | |
| Analog Out 3 | To enable modulating cooling conditioning | Heating | |
| Analog Out 4 | To enable modulating outside Air Control | Outside Air Damper | |
| Relay 3 | To enable Fan Enable control | Fan Enable |
Humidifier Dehumidifier O-Energize in Cooling B- Energize in Heating Fan Enable Occupied Enable DCV Damper |
| Relay 7 | To enable Humidifier/Dehumidifier Enable control | Humidifier Enable | |
| Thermistor 1 | To enable sensor value monitoring | Supply Air Temperature |
Thermistor Input Supply Air Temperature Fan Run Status NO Fan Run Status NC
|
| Thermistor 2 | To enable sensor value monitoring | Thermistor Input | |
| Analog In 1 | To enable valve position feedback / Current TX consumption / Voltage input monitoring | Voltage Input |
Voltage Input Heating Valve Position Feedback Cooling Valve Position Feedback Current TX (0-10Amps) Current TX (0-20Amps) Current TX (0-30Amps) Current TX (0-50Amps) Current TX (0-60Amps) Current TX (0-100Amps) Current TX (0-120Amps) Current TX (0-150Amps) Current TX (0-200Amps) |
| Analog In 1 | To enable valve position feedback / Current TX consumption / Voltage input monitoring | Heating Valve Position |
Once you've configured the system profile as a VAV system, the sequences for VAV applications in GPC36 will be followed. You will need to select a few specific configuration parameters that define the physical characteristics AHU.
| Control System Object List
| Object Name | Type | Input/Output Type/ Default Value |
| Current Temp | Input (Terminal Side) | Average Current Temperature of Zones |
| Humidity | Input (Terminal Side) | Average Humidity of Zones |
| Zone Base Priority | User Intent (Terminal Side) | NA |
| coolingSATMinimum (SATspMin) | Tuner | 55 F |
| coolingSATMaximum (SATspMin) | Tuner | 65 F |
| coolingPreconditioningRate | Tuner | 15 mins |
| heatingPreconditioningRate | Tuner | 15 mins |
| zonePriorityMultiplier | Tuner | 1.30 |
| zonePrioritySpread | Tuner | 2 |
| Cooling Desired Temperature | User Intent (Terminal side) | NA |
| Heating Desired Temperature | User Intent (Terminal side) | NA |
| Conditioning Mode | User Intent | NA |
| Operation Mode | Calculated Input | NA |
| Fan Mode | User Intent | NA |
| Occupancy Mode | Input |
Schedule / Terminal OWI Sensors |
| Cooling Stage 1 | Output | Control Mote Relay |
| Cooling Stage 2 | Output | Control Mote Relay |
| Cooling Stage 3 | Output | Control Mote Relay |
| Cooling Stage 4 | Output | Control Mote Relay |
| Cooling Stage 5 | Output | Control Mote Relay |
| Heating Stage 1 | Output | Control Mote Relay |
| Heating Stage 2 | Output | Control Mote Relay |
| Heating Stage 3 | Output | Control Mote Relay |
| Heating Stage 4 | Output | Control Mote Relay |
| Heating Stage 5 | Output | Control Mote Relay |
| Fan Speed 1 | Output | Control Mote Relay |
| Fan Speed 2 | Output | Control Mote Relay |
| Fan Speed 3 | Output | Control Mote Relay |
| Fan Speed 4 | Output | Control Mote Relay |
| Fan Speed 5 | Output | Control Mote Relay |
| Humidifier | Output | Control Mote Relay |
| Dehumidifier | Output | Control Mote Relay |
| Modulating Cooling | Output | Control Mote AnalogOut |
| Modulating Heating | Output | Control Mote AnalogOut |
| Modulating Fan Speed | Output | Control Mote AnalogOut |
| coolingPreconditioningRate | Tuner | 15 mins |
| heatingPreconditioningRate | Tuner | 15 mins |
| zonePriorityMultiplier | Tuner | 1.30 |
| zonePrioritySpread | Tuner | 2 |
Note: For a comprehensive list of tuners and their details refer to Tuners Complete List
| Sequence of Operation
The sequence of operation is completely driven based on Occupancy mode, and Zone Loads (Cooling/Heating).
Let us understand the Sequence of operations based on the occupancy modes, and how the other factors contribute to the sequence of operations during different types of occupancy modes.
| Occupancy Modes
The occupancy mode (Occupied or Unoccupied) shall be determined through a user-adjustable, graphical, seven-day schedule with a holiday schedule.
Based on the above aspects factoring into the occupancy the following can be the possible applicable occupancy modes:
- Pre- Conditioning
- Occupied
- Unoccupied
| Sequence of Operation During Pre-Conditioning
Pre-conditioning is a state just before the building enters the scheduled occupancy. It starts at more like the unoccupied state, the desired temperatures drift to unoccupied setbacks.
The preconditioning uses an algorithm to start the conditioning before the building is scheduled for occupancy, from the heating side or cooling side, to bring the building to an optimum level ( within the occupied heating & cooling desired temperatures) exactly at the time of occupancy start.
A coolingPreconditioningRate and heatingPreconditiningRate tuners defaulted to 15 minutes, are used alongside the occupied heating/cooling desired temperature breach to determine when the pre-conditioning should start.
Example Calculation:
When,
-
- The heating & cooling desired temperatures (Average of zones needing conditioning) are 70F and 74F for the building.
- The operating mode is determined based on the weighted average calculation as shown in section | Sequence of Operation During Occupied
Let us assume:
-
-
- The operating mode determined is cooling.
- The current temperature (Average of zones needing cooling conditioning) is 76F
- 8:00 AM is the time the building is scheduled to be occupied.
-
Then the preconditioning start time is calculated as follows:
Cooling Desired Temperature Breach= 76-74=2F
Preconditioning duration= coolingPreconditioningRate (mins) * Cooling Desired Temperature Breach
= 15*2
= 30 mins
The preconditioning starts 30 minutes before the building is scheduled to be occupied, which is = 7:30 AM.
The zones operate the damper positions optimally to receive the required conditioning to satisfy their load requirements to maintain a temperature within the deadband.
For more information on the damper operations, refer to VAV Terminal Profile- Damper Position Calculation & Operation.
| Sequence of Operation During Occupied
During the scheduled Occupied times, the AHU/RTU is influenced by two aspects of the system.
- The Operating Mode
- The Conditioning Mode
Conditioning Modes
The Operating mode is a user intent parameter that the user can specify. There are four types of operating modes.
- Off
- Auto
- Cooling
- Heating
Operating Modes
The Conditioning mode is a derived parameter. There are three types of conditioning modes.
- Cooling
- Heating
- Off
Based on the influence of the aspects mentioned above, the device supplies the cooling/ heating load requirements, and the zones operate the damper positions optimally to receive the required conditioning to satisfy their load requirements and maintain a temperature within the deadband.
For more information on the damper operations, refer to VAV Terminal Profile- Damper Position Calculation & Operation.
Weighted Average Load MA (Heating /Cooling)
weightedAverageHeatingOnlyLoadMA/ weightedAverageCoolingOnlyLoadMA, is a result of the following steps.
| Step | Formula/Calculation |
| Heating Load/Cooling Load |
When the zone's current temperatures fall below the HeatingDesiredTemperatures they contribute to the zone heating load
|
| Dynamic Priority (Heating/Cooling) |
Note: The exponent (zoneHeatingLoad/zonePrioritySpread) or (zoneCoolingLoad/zonePrioritySpread) will be limited to the max value of 10. This will prevent a zone with large temperature drift (probably because of faulty sensors) from driving system operation. |
| Weighted Average (Heating/Cooling) |
|
| Weighted Average Post ML (Machine Learning) (Heating/Cooling |
|
|
Weighted Average MA (Moving Average) (Heating/Cooling) |
is then put through a 15-minute moving average filter (which takes the last 15, minute readings and then averages them) to reduce sudden swings to get the weightedAverageLoadMA) |
Operating Mode Determination
Conditioning mode is determined using the following table:
| If | Then |
| weightedAverageCoolingOnlyLoadMA is zero and weightedAverageHeatingOnlyLoadMA is positive. |
|
|
weightedAverageHeatingOnlyLoadMA is zero. weightedAverageCoolingOnlyLoadMA is positive. |
|
|
weightedAverageHeatingOnlyLoadMA is zero. weightedAverageCoolingOnlyLoadMA is zero.
|
The system is within the deadband, there is neither a cooling load nor a heating load, hence there is no conditioning that occurs at the AHU end, except for a minimum mechanical or free ventilation. |
| Sequence of Operation During UnOccupied
- The range of Heating Desired Temperature and Cooling Desired Temperature of the zones drifts further away to unoccupied setback.
- The device supplies for the cooling/Heating load requirements of the zones, and the zones operate the damper positions optimally to receive the required conditioning to satisfy their load requirements to maintain the room temperature within the newly set autoaway setback temperature range, for more information on the damper operations refer to VAV Terminal Profile- Damper Position Calculation & Operation.
- If weightedAverageHeatingOnlyLoadMA/ weightedAverageCoolingOnlyLoadMA, is a positive value. The system operates in the determined conditioning mode to supply the zone cooling/heating load requirements, as shown in the | Sequence of Operation During Occupied
- If weightedAverageHeatingOnlyLoadMA & weightedAverageCoolingOnlyLoadMA, is zero. The system is within the deadband, there is neither a cooling load nor a heating load, hence there is no conditioning that occurs at the AHU end, except for a minimum mechanical or free ventilation.
| Sequence of Operation During Emergency Conditioning
When zone limits are violated, and the recorded temperature is within the zone limit plus leeway the conditioning will happen in the direction of zone load, as shown in the cooling conditioning, or Heating conditioning mode.
| Sequence of Operation During Zone Temp Dead
And, When the zone temperature breaches the zone limits, beyond the leeway limits all the following loops are disabled:
-
- CoolingLoopOutput
- HeatingLoopOutput
- FanLoopOutput
| Humidifier Control
The humidifier is turned ON whenever the humidity level for the system drops below the targetMinInsideHumidty set. The humidifier will be turned OFF after being turned on when the humidity levels go humidityHysteresis above the targetMinInsideHumidty. Humidity control will not be maintained during UNOCCUPIED or VACATION modes.
| DeHumidifier Control
If the dehumidifier is selected, it turns ON whenever the humidity level for the system goes above the targetMaxInsideHumidty set. The dehumidifier will be turned OFF after being turned on when the humidity drops humidityHysteresis below the targetMaxInsideHumidty. Dehumidifier control will not be maintained during UNOCCUPIED or VACATION modes.
Note: The humidity level for the system is either the average level reported by all the zones serviced by the RTU/AHU.
| Operation Mode Summary
|
Modes & Operation |
Pre-Conditioning | Occupied | Unoccupied |
| Auto |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput
|
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
| Heat Only | HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput
|
HeatingLoopOutput FanLoopOutput |
| Cool Only |
CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanloopOutput
|
CoolingLoopOutput FanLoopOutput |
| Off | All Loops Deactivated |
||
| Control Trigger Examples
Cooling
When the zones demand for cooling the algorithm calculates a loop output, which is based on the Proportional and Integral loop for control signals, called cooling loop output. This loop output which is in percentage is scaled to modulating cooling
Heating
When the zones demand for heating the algorithm calculates a loop output, which is based on the Proportional and Integral loop for control signals, called Heating loop output. This loop output which is in percentage, is scaled to the different modulating cooling.
Fan
The modulating fan control is triggered as per cooling or heating loop output..
Recirculate
When the zone demands recirculation along with cooling, the system will call for the stage-1 fan and so on for fan speed which is also based on the loop output that is calculated.
Comments
0 comments
Please sign in to leave a comment.