4 Minute Read
| Overview
The VAV with Reheat (No Fan) profile is a terminal unit profile that uses a SmartNode to control a VAV terminal box. It supports both the cooling and heating requirements of a zone.
Based on the operating mode of the system-level equipment (AHU or RTU), the profile automatically adjusts the damper position and reheat operation to deliver optimal zone comfort. When the AHU or RTU is in cooling mode, the damper modulates to satisfy the cooling demand. When the system is in heating mode, the profile coordinates the damper, fans and reheat operation to efficiently meet the zone's heating requirements while maintaining occupant comfort.
The profile also supports the Enable MySense setting, which makes the MySense universal inputs available for configuration. Each input can be enabled independently and mapped to a supported sensor or device.
| How it Works
The VAV with Reheat-Parallel Fan allows selection of dampers and reheat based on the equipment used and zone priority, which corresponds to the importance multiplier in Guideline 36.
On the heating side, the profile supports both the staged & modulating reheat controls.
| Quick Summary | |
| Modulating Damper Control | Reset based on Space Temperature and/or CO2 and/or CFM & mode of operation. |
| Modulating / Stages Reheat Control | Reset based on Space Temperature & mode of operation at the system level |
| Parallel Fan Speed Control | Reset based on Space Temperature and/or CO2 and/or CFM & mode of operation. |
| Wiring
Wiring Schematic for Modulating Hot Water Reheat
Wiring Schematic for Modulating Electric Reheat
Wiring Schematic for Staged Electric Reheat
For more wiring information, refer to the CDDs attached.
| Configuration Steps
To configure a VAV with a Reheat (Parallel Fan) profile
- Click the pair module from the floor layout screen.
- Click the SN (SmartNode) from the select device type screen.
- Click the VAV with Reheat from the select module type, screen.
- Select the VAV Reheat- Parallel Fan.
- Click Pair, to pair the device using the pairing instructions on the pairing steps screen.
- Select the device MAC address relayed for pairing, or click connect manually to pair the device manually. For more information on manual pairing refer to Alternate/ Manual Pairing for SmartNode.
- Enter the pin displayed on the SmartNode device or an automatic pairing.
- Click Pair.
The profile configuration screen is displayed as below.
| Profile Configuration
After the SmartNode is paired, the VAV with Reheat (Parallel Fan) profile configuration screen is displayed.
The profile configuration screen contains the following sections:
- General Settings
- SmartNode I/O Configuration
- MySense Configuration
- TrueCFM Configuration
- Damper Position Configuration
- Save and Cancel
General Settings
| No. | Parameter | Description | Range | Default |
|---|---|---|---|---|
| 1 | Temperature Offset | Applies an offset to the measured zone temperature used by the control algorithm. | -10 to 10 (0.1 increments) | 0 |
| 2 | Auto Forced Occupied | Conditions the zone when occupancy is detected outside the occupied schedule. | Enabled / Disabled | Disabled |
| 3 | Auto Away | Suspends zone conditioning when the zone is unoccupied during the occupied schedule. | Enabled / Disabled | Disabled |
| 4 | CO₂ Control | Enables demand-controlled ventilation using the configured CO₂ input. Available regardless of MySense configuration. | Enabled / Disabled | Disabled |
| 5 | Enable TrueCFM Control | Enables TrueCFM-based airflow control. Additional TrueCFM parameters become available when enabled. For additional information, Refer to TrueCFM Configuration Section. | Enabled / Disabled | Disabled |
Damper Shape
Damper Shape defines the geometry of the installed VAV damper. The selected shape determines the dimension parameters displayed in the configuration screen.
| Damper Shape | Displayed Parameter | Available Values |
|---|---|---|
| Square | Damper Size | 4–22 (increments of 2) |
| Rectangle | Damper Width, Damper Height | 1–22 |
| Round | Damper Diameter | 1–22 |
Default:
- Damper Shape: Round
- Damper Diameter: 1
Zone Priority
Zone Priority defines the weighting applied to zone-generated Trim-and-Respond requests.
| Option | Value | Description |
|---|---|---|
| No Priority | 0 | The zone does not generate Trim-and-Respond requests. |
| Low | 0.1 | Generates requests at one-tenth of the normal rate. |
| Normal | 1 | Generates requests at the normal rate. |
| High | 5 | Generates requests at five times the normal rate. |
Default: Normal
For additional information, refer to Damper Position & Zone Priority Driven Trim and Respond Requests.
Enable Wireless Door/Window Sensor
Enable Wireless Door/Window Sensor enables support for a compatible wireless door/window sensor.
Default: Disabled
When enabled, the Sensor Type field becomes available.
Available options:
- Door Window Sensor
- Door Window Sensor – Title 24
SmartNode I/O Configuration
The SmartNode provides physical analog outputs, relay outputs, and universal inputs that can be configured for the VAV with Reheat (Parallel Fan) profile. Depending on the profile requirements, I/O points may be fixed or configurable.
The SmartNode provides the following I/O points:
- Four Analog Outputs (AO1–AO4)
- Four Relay Outputs (RL1–RL4)
- Four Universal Inputs (UI1–UI4)
For configurable I/O points, the mapping field is available only after the corresponding I/O point is enabled.
Analog Outputs
The SmartNode provides four analog-output terminals.
| Analog Output | Default Status | Default Mapping |
|---|---|---|
| AO1 | Enabled | Damper (0–10 V) |
| AO2 | Disabled | Modulating Reheat (0–10 V) |
| AO3 | Disabled | Externally Mapped |
| AO4 | Disabled | Externally Mapped |
AO1 is enabled by default to control the damper actuator. AO2, AO3, and AO4 are disabled by default and can be enabled as required.
Available analog-output mappings include:
- Damper (0–10 V)
- Damper (2–10 V)
- Damper (10–0 V)
- Damper (10–2 V)
- Damper (0–5 V)
- Modulating Reheat (0–10 V)
- Modulating Reheat (2–10 V)
- Modulating Reheat (10–0 V)
- Modulating Reheat (10–2 V)
- Externally Mapped
Damper and Modulating Reheat functions can be assigned to any enabled analog output.
Relay Outputs
The SmartNode provides four relay-output terminals that support Parallel Fan operation and staged electric reheat.
RL2 is enabled and mapped to Parallel Fan by default.
| Relay Output | Default Status | Default Mapping |
|---|---|---|
| RL1 | Disabled | Stage 1 Reheat |
| RL2 | Disabled | Parallel Fan |
| RL3 | Disabled | Stage 2 Reheat |
| RL4 | Disabled | Stage 3 Reheat |
Available relay mappings include:
- Parallel Fan
- Stage 1 Reheat
- Stage 2 Reheat
- Stage 3 Reheat
- Externally Mapped
Mapping Validation for Relay outputs
The Parallel Fan function can be assigned to any relay output. Although multiple relay outputs can be configured as Parallel Fan, configuring a single relay output for the Parallel Fan function is the recommended configuration.
The remaining relay outputs can be configured for Stage 1, Stage 2, and Stage 3 Reheat. Reheat stages shall be assigned in sequential order. Relay outputs configured as Parallel Fan are excluded from the reheat-stage sequencing validation.
| Relay Configuration | Result |
|---|---|
| RL1 = Stage 1, RL2 = Parallel Fan, RL3 = Stage 2, RL4 = Stage 3 | Valid |
| RL1 = Parallel Fan, RL2 = Stage 1, RL3 = Stage 2, RL4 = Stage 3 | Valid |
| RL1 = Stage 1, RL2 = Stage 2, RL3 = Parallel Fan, RL4 = Stage 3 | Valid |
| RL1 = Stage 1, RL2 = Stage 3, RL3 = Parallel Fan, RL4 = Stage 3 | Invalid |
If the configured relay stages do not meet the sequencing requirement, the CCU displays the following validation message:
"Reheat stages for relays should be configured sequentially."
Universal Inputs
The SmartNode provides four universal-input terminals. Depending on the selected mapping, a universal input operates as either a thermistor input or an analog input.
| Universal Input | Default Status | Default Mapping | Configuration |
|---|---|---|---|
| UI1 | Enabled | Damper Feedback | Fixed |
| UI2 | Disabled | Voltage Input | Configurable |
| UI3 | Enabled | Discharge Air Temperature | Fixed |
| UI4 | Enabled | Entering Air Temperature | Fixed |
UI1, UI3, and UI4 are fixed assignments required by this profile. Only UI2 is configurable.
The available mapping options are limited to analog input types.
Analog Input
- Damper Feedback
- Voltage Input
- Current TX (0–10 Amps)
- Current TX (0–20 Amps)
- Modulating Reheat Feedback
Mapping Validation for Universal inputs
Modulating Reheat Feedback
When Modulating Reheat is assigned to an analog output, Modulating Reheat Feedback shall also be assigned to a universal input.
For this profile, Modulating Reheat Feedback shall be mapped to UI2.
If the feedback input is not configured, the CCU displays the following validation message:
"Please map the Modulating Reheat Feedback sensor to a universal input to continue."
Duplicate Sensor Mapping
Each sensor function can be assigned to only one universal input.
The following mappings are fixed for this profile:
- UI1 – Damper Feedback
- UI3 – Discharge Air Temperature
- UI4 – Entering Air Temperature
These functions shall not be assigned to UI2.
If a duplicate mapping is detected, the CCU displays the following validation message:
"Each sensor can only be mapped once. Please check your mappings."
If Modulating Reheat Feedback is not assigned when required, the Modulating Reheat Feedback validation message takes precedence over the duplicate sensor validation.
MySense Configuration
Enable MySense is disabled by default.
When enabled, three configurable MySense universal inputs are displayed.
| Universal Input | Default Status | Default Mapping |
|---|---|---|
| UI1 | Disabled | Door/Window Sensor N/C |
| UI2 | Disabled | Current TX (0–10 Amps) |
| UI3 | Disabled | Generic Alarm N/O |
Each input can be enabled independently. The mapping list is displayed after the corresponding input is enabled.
The following mappings are available.
- Voltage Input
- Damper Feedback
- Current TX (0–10 Amps)
- Current TX (0–20 Amps)
- Thermistor Input
- Discharge Air Temperature
- Entering Air Temperature
- Generic Alarm N/O
- Generic Alarm N/C
- Door/Window Sensor – N/O
- Door/Window Sensor – N/C
- Door/Window Sensor – N/O – Title 24
- Door/Window Sensor – N/C – Title 24
- Modulating Reheat Feedback
Control Inputs
The following mappings are used by the VAV with Reheat (Parallel Fan) control sequence.
- Door/Window Sensor – N/O
- Door/Window Sensor – N/C
- Door/Window Sensor – N/O – Title 24
- Door/Window Sensor – N/C – Title 24
All other mappings are used for monitoring only.
Configure the door/window sensor mapping to match the installed device.
Enable MySense Icon Mode
Enable MySense Icon Mode is displayed only when Enable MySense is enabled.
Default: Disabled
TrueCFM Configuration
The TrueCFM Configuration section defines the airflow limits and damper-position limits used by the VAV with Reheat (Parallel Fan) profile when Enable TrueCFM Control is enabled.
For information about the airflow calculation and damper control algorithm, refer to VAV Terminal Profile- Damper Position Calculation & Operation.
CFM Settings
The CFM settings define the airflow limits for cooling and reheating operation.
| Setting | Default | Range |
|---|---|---|
| Min CFM Cooling | 50 CFM | 0–5000 CFM (5 CFM increments) |
| Max CFM Cooling | 250 CFM | 0–5000 CFM (5 CFM increments) |
| Min CFM Reheating | 50 CFM | 0–5000 CFM (5 CFM increments) |
| Max CFM Reheating | 250 CFM | 0–5000 CFM (5 CFM increments) |
K-Factor
The K-Factor defines the airflow coefficient used by the TrueCFM control algorithm.
| Setting | Default | Range |
|---|---|---|
| K-Factor | 2.0 | 0.00–10.00 (0.01 increments) |
The K-Factor parameter is displayed only when Enable TrueCFM Control is enabled.
Damper Position Configuration
The available damper-position parameters depend on the state of Enable TrueCFM Control.
TrueCFM Enabled
When Enable TrueCFM Control is enabled, the following heating damper-position limits are available.
| Setting | Default | Range |
|---|---|---|
| Min Damper Position Heating | 20% | 0–100% (1% increments) |
| Max Damper Position Heating | 100% | 0–100% (1% increments) |
TrueCFM Disabled
When Enable TrueCFM Control is disabled, separate cooling and heating damper-position limits are available.
| Setting | Default | Range |
|---|---|---|
| Min Damper Position Cooling | 20% | 0–100% (1% increments) |
| Max Damper Position Cooling | 100% | 0–100% (1% increments) |
| Min Damper Position Heating | 20% | 0–100% (1% increments) |
| Max Damper Position Heating | 100% | 0–100% (1% increments) |
Save the Configuration
After completing all required profile settings, select Save. The SmartNode pairing and VAV with Reheat (Parallel Fan) profile configuration are then completed.
| Control System Object List
| Object Name | Type | Input/Output Type |
| Heating Desired Temp | User Intent | NA |
| Cooling Desired Temp | User Intent | NA |
| Current Temp | Input | OWI Sensor |
| Humidity | Input | OWI Sensor |
| Occupancy Mode | Input |
OWI Sensor |
| CO2 | Input |
OWI Sensor |
| Damper Actuator | Output | SmartNode Analog Out |
| Reheat Stage 1 | Output | SmartNode Relay |
| Reheat Stage 2 | Output | SmartNode Relay |
| Modulating Reheat | Output | SmartNode Analog Out |
| Zone Priority | Input | User Intent/ Configuration Setup |
| Damper Size & Shape | Input | User Intent/ Configuration Setup |
| Discharge Airflow Temperature | Input | SmartNode Thermistor |
| Supply Airflow Temperature | Input | SmartNode Thermistor |
| Minimum Damper Position Cooling | Input | User Intent/ Configuration Setup |
| Maximum Damper Position Cooling | Input | User Intent/ Configuration Setup |
| Minimum Damper Position Heating | Input | User Intent/ Configuration Setup |
| Maximum Damper Position Heating | Input | User Intent/ Configuration Setup |
| Minimum CFM Cooling | Input | User Intent/ Configuration Setup |
| Maximum CFM Cooling | Input | User Intent/ Configuration Setup |
| Minimum CFM Reheat | Input | User Intent/ Configuration Setup |
| Maximum CFM Reheat | Input | User Intent/ Configuration Setup |
| Maximum Damper Heating | Input | User Intent/ Configuration Setup |
| reheatZoneMaxDischargeTemp | Tuner | 90 F |
| coolingPreconditioningRate | Tuner | 15 Mins |
| heatingPreconditioningRate | Tuner | 15 Mins |
Note: For a comprehensive list of tuners and their details refer to Tuners Complete List.
| Sequence of Operation
The sequence of operation is completely driven based on Occupancy mode, Space Current Temperature, the set Cooling and Heating Desired Temperatures, CFM, and Space CO2 levels.
Let us understand the Sequence of operations based on the occupancy modes, and how the other factors contribute to the sequence of operations during different types of occupancy modes.
| Occupancy Modes
The occupancy mode (Occupied or Unoccupied) shall be determined through a user-adjustable, graphical, seven-day schedule with a holiday schedule, alongside the configurable autoaway and forced occupied options (external schedule influencers) for optimized controls and enhanced energy savings.
Based on the above aspects, factoring in the occupancy the following can be the possible applicable occupancy modes:
- Pre- Conditioning
- Occupied
- Unoccupied
- Auto-Away
- Forced Occupied
| Sequence of Operation During Pre-Conditioning
Pre-conditioning is a state just before the building enters the scheduled occupancy. It starts at more like the unoccupied state, the desired temperatures drift to unoccupied setbacks.
The preconditioning uses an algorithm to start the conditioning before the building is scheduled for occupancy, from the heating side or cooling side, to bring the building to an optimum level ( within the occupied heating & cooling desired temperatures) exactly at the time of occupancy start.
A cooling and heating coolingPreconditioningRate and heatingPreconditiningRate tuners defaulted to 15 minutes, are used alongside the occupied heating/cooling desired temperature breach to determine when the pre-conditioning should start.
Example Calculation:`
When,
- The heating & cooling desired temperatures are 70F and 74F for the building,
- The current temperature is 76F (Average of zone temperatures),
- 8:00 AM is the time the building is scheduled to be occupied.
Then the preconditioning start time is calculated as follows:
Cooling Desired Temperature Breach= 76-74=2F
Preconditioning duration= coolingPreconditioningRate (mins) * Cooling Desired Temperature Breach
= 15*2
= 30 mins
The preconditioning starts 30 minutes before the building is scheduled to be occupied, which is = 7:30 AM.
The zones would operate as shown below to accommodate the preconditioning from the system equipment.
During Warm-up:
- If the space temperature is below the occupied heating desired temperature, the space utilizes the warm-up via HeatingLoopOutput as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The Damper remains at a minimum |
The HeatingLoopOutput is mapped to the Damper position actuator For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 loops are disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Pre-cooling:
- If the space temperature is below the occupied cooling desired temperature, the space utilizes the morning pre-cooling via CoolingLoopOutput, as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position |
- The CO2 loops are disabled. (If configured for)
| Sequence of Operation During Occupied
At all occupied times: (based on a set schedule)
- The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
| Configuration | Damper Operation |
| If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
| If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
| If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
| If zone Temperature, CO2 & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space current temperature falls below the HeatingDesiredTemperature the HeatingLoopOutput is enabled as below as below.
| If System Equipment is in Cooling Mode | If System Equipment in Heating Mode |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation
|
During Cooling:
- When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled, as below
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Positio |
| Sequence of Operation During AutoAway
- The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
- The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
- CoolingLoopOutput, HeatingLoopOutput, CFM LoopOutput, CO2 Loop Output, and Reheat Stages are disabled.
During Heating:
- When the space current temperature falls below the heating autoaway setback temperature, the HeatingLoopOutput is enabled as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 loop is disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current is above the cooling the CoolingLoopOutput is enabled, as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 loop is disabled. (If configured for)
| Sequence of Operation During Unoccupied
- The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
- The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
| Configuration | Damper Operation |
| If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
| If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
| If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
| If zone Temperature, CO2 & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space's current temperature falls below the heating the HeatingLoopOutput is enabled as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 loop is disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current temperature is above the cooling the CoolingLoopOutput is enabled, as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 loop is disabled. (If configured for)
| Sequence of Operation During Forced Occupied
- The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.
During Deadband:
During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.
| Configuration | Damper Operation |
| If only the zone temperature-based configuration is enabled. |
The damper shall be at its minimum position and the reheat valve will remain closed. The Dmaper minimum is decided based on the last known conditioning,
|
| If zone Temperature & CO2-based configuration is enabled. |
The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true. |
| If zone Temperature & CFM-based configuration is enabled. | The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
| If zone Temperature, CO2 & CFM-based configuration is enabled. | The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
During Heating:
- When the space current temperature falls below the Heating Desired Temperature the HeatingLoopOutput is enabled as below.
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90) Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
- The CO2 loop is disabled. (If configured for)
- The CFM loop is disabled. (If configured for)
During Cooling:
- When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled as below,
| If System Equipment in Cooling Mode | If System Equipment in Heating Mode |
|
The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling. For more information on the Damper position calculation refer to VAV Terminal Profile- Damper Position Calculation & Operation The CFM loop is enabled (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to VAV Terminal Profile- Damper Position Calculation & Operation |
The Damper position moves to the minimum position, not allowing further hot air into the room. The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm) |
- The CO2 loop is disabled. (If configured for)
| Sequence of Operation During Emergency Conditioning
When zone limits are violated, and the recorded temperature is within the zone limit plus leeway the conditioning will happen in the direction of zone load.
| Sequence of Operation During Zone Temp Dead
And, when the zone temperature breaches the zone limits, beyond the leeway limits all the following loops are disabled:
- CoolingLoopOutput
- HeatingLoopOutput
- Reheat Stages
- FanLoopOutput
- CO2 & IAQ LoopOutput
- CFM LoopOutput
| Control Mode Summary
|
Modes & Operation |
Pre-Conditioning | Occupied | AutoAway | Unoccupied | Forced Occupied |
| Auto |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput CFMLoopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput CFMLoopOutput CO2LoopOutput IAQLoopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
HeatingLoopOutput FanLoopOutput CoolingLoopOutput FanloopOutput |
| Heat Only | HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput |
HeatingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
| Cool Only |
CoolingLoopOutput FanLoopOutput CFMLoopOutout |
CoolingLoopOutput FanloopOutput CFMLoopOutput CO2LoopOutput IAQLoopOutput |
CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput |
CoolingLoopOutput FanLoopOutput CO2LoopOutput IAQLoopOutput |
| Off | All Loops Deactivated |
||||