| Overview

The DAB terminal profile is a profile that controls the terminal equipment of a space, which is provided by an RTU or an AHU for its HVAC needs. The profile is supported by a SmartNode, a Smart Damper, and a Smart Damper Actuator to provide the necessary control outputs based on the profile configured.

The profile also supports the Enable MySense setting, which makes the MySense universal inputs available for configuration. Each input can be enabled independently and mapped to a supported sensor or device.

| How it Works

75F Dynamic Airflow Balancing operates to help temperature balance a system without fully closing off zones and creating harmful back pressure on the AHU.

Once you select the DAB terminal profile under SmartNode DAB profiles, the configuration provides the options to define the damper types, size, shape, and zone priority. It also provides the options to define the minimum and maximum damper positions during heating and cooling along with the Temperature Offset.

Additionally, the profile provides options to modify the controls based on the Internal Air Quality and Co2, with the IAQ and Co2 control that can be enabled or disabled.

Normally the Algorithm continuously tracks the current temperature of the zone and looks for the change in the difference between the terminal level Desired Temperature and Current Temperature and provides an optimal damper opening position within the deadband range, which is a resultant of the loop output based on the PI loop for control signals.

When the Current Temperature increases above the set point or desired temperature, the zone calls for cooling from the system or building-level equipment. 

And when the Current Temperature decreases below the set point or desired temperature, the zones call for Heating from the system or building-level equipment.

The building or system-level device is an RTU or AHU which is controlled by the system-level DAB profiles.

For more information on the system-level DAB, profiles refer below.

DAB Staged RTU - Wiring/ Configuration

DAB Fully Modulating AHU - Wiring/ Configuration

DAB Modulating AHU with DCWB

DAB Advanced Hybrid AHU - Wiring/ Configuration

When the Co2 or the IAQ control is enabled, the algorithm takes the target and threshold values of Co2 and VOC into consideration. An increase in the value from the threshold value results in a loop output, and it changes the minimum damper position for the actual control to the changes in percentage value.

This resultant loop output is called the Co2 loop output, which is simply the weighted average Co2 loop output for all the zones that have Co2 control enabled.

Example- If the target and threshold are 1000ppm and 800, measured Co2 is 850 and configured damper limits are 0-100.  The algorithm starts raising the minimum damper position proportionally from 800.  A Co2 measurement of 850 will yield a loop output of 25%. This raises the damper's min position so that it now varies in the range of 25 – 100 based on temperature.

| Wiring

Below is a wiring schematic for the DAB terminal profile that shows the connection between the SmartNode.

For more wiring information, refer to the CDDs attached.

| Configuration Steps

To configure a DAB Terminal Profile.

  • Click the pair module from the floor layout screen.
  • Click the SN (SmartNode) from the select device type screen.
  • Click the DAB from the select module type, screen.
  • Select the DAB Profile under DAB.
  • Click Pair, to pair the device using the pairing instructions on the pairing steps screen.

  • Enter the pin displayed on the SmartNode device or an automatic pairing.
  • Click Pair.

Below is the configuration screen for the DAB terminal profile.

Once you've paired the SmartNode as a DAB profile, and once a few specific configuration parameters that define the physical characteristics of the setup are set in the configuration screen, the 75F sequence for the DAB will influence and control the setup. 

| Profile Configuration

After the SmartNode is paired, the DAB profile configuration screen is displayed.

The profile configuration screen contains the following sections:

  • General Settings
  • SmartNode I/O Configuration
  • MySense Configuration
  • TrueCFM Configuration
  • Damper Position Configuration
  • Save and Cancel

General Settings

No. Parameter Description Range Default
1 Temperature Offset Applies an offset to the measured zone temperature used by the control algorithm. -10 to 10 (0.1 increments) 0
2 Auto Forced Occupied Conditions the zone when occupancy is detected outside the occupied schedule. Enabled / Disabled Disabled
3 Auto Away Suspends zone conditioning when the zone is unoccupied during the occupied schedule. Enabled / Disabled Disabled
4 CO₂ Control Enables demand-controlled ventilation using the configured CO₂ input. Available regardless of MySense configuration. Enabled / Disabled Disabled
5 Enable TrueCFM Control Enables TrueCFM-based airflow control. Additional TrueCFM parameters become available when enabled. For additional information, Refer to TrueCFM Configuration Section. Enabled / Disabled Disabled

Damper Shape

Damper Shape defines the geometry of the installed dampers. The DAB (Dual Airflow Balance) profile supports configuration of two dampers independently. Each damper can be configured based on the installed damper shape and dimensions. The selected shape determines the dimension parameters displayed in the configuration screen.

Damper Shape Displayed Parameter Available Values
Square Damper Size 4–22 (increments of 2)
Rectangle Damper Width, Damper Height 1–22
Round Damper Diameter 1–22

Default:

  • Damper Shape: Round
  • Damper Diameter: 1

Zone Priority

Zone Priority defines the weighting applied to zone-generated Trim-and-Respond requests.

Option Value Description
No Priority 0 The zone does not generate Trim-and-Respond requests.
Low 0.1 Generates requests at one-tenth of the normal rate.
Normal 1 Generates requests at the normal rate.
High 5 Generates requests at five times the normal rate.

Default: Normal

For additional information, refer to Damper Position & Zone Priority Driven Trim and Respond Requests.

Enable Wireless Door/Window Sensor

Enable Wireless Door/Window Sensor enables support for a compatible wireless door/window sensor.

Default: Disabled

When enabled, the Sensor Type field becomes available.

Available options:

  • Door Window Sensor
  • Door Window Sensor – Title 24

 

SmartNode I/O Configuration

The SmartNode provides physical analog outputs, relay outputs, and universal inputs that can be configured for the DAB profile. Depending on the profile requirements, I/O points may be fixed or configurable.The SmartNode provides the following I/O points:

  • Four Analog Outputs (AO1–AO4)
  • Four Relay Outputs (RL1–RL4)
  • Four Universal Inputs (UI1–UI4)

For configurable I/O points, the mapping field is available only after the corresponding I/O point is enabled.

 

Analog Outputs

The SmartNode provides four analog-output terminals.

Analog Output Default Status Default Mapping
AO1 Enabled Damper 1 (0–10 V)
AO2 Enabled Damper 2 (0–10 V)
AO3 Disabled Modulating Reheat (0–10 V)
AO4 Disabled Externally Mapped

AO1 and AO2 is enabled by default to control the damper actuators. AO3 and AO4 are disabled by default and can be enabled as required.
 

Available analog-output mappings include:

  • Damper 1 (0–10 V)
  • Damper 1 (2–10 V)
  • Damper 1 (10–0 V)
  • Damper 1 (10–2 V)
  • Damper 1 (0–5 V)
  • Damper 2 (0–10 V)
  • Damper 2 (2–10 V)
  • Damper 2 (10–0 V)
  • Damper 2 (10–2 V)
  • Damper 2 (0–5 V)
  • Modulating Reheat (0–10 V)
  • Modulating Reheat (2–10 V)
  • Modulating Reheat (10–0 V)
  • Modulating Reheat (10–2 V)
  • Externally Mapped

Damper 1, Damper 2 and Modulating Reheat functions can be assigned to any enabled analog output.

 

Relay Outputs

The SmartNode provides four relay-output terminals that support staged electric reheat.

All relay outputs are disabled by default.

Relay Output Default Status Default Mapping
RL1 Disabled Stage 1 Reheat
RL2 Disabled Stage 2 Reheat
RL3 Disabled Stage 3 Reheat
RL4 Disabled Stage 4 Reheat

 

Available relay mappings include:

  • Stage 1 Reheat
  • Stage 2 Reheat
  • Stage 3 Reheat
  • Stage 4 Reheat
  • Externally Mapped

Mapping Validation for Relay outputs

Enabled relay outputs shall be assigned in sequential reheat-stage order. Duplicate stage assignments are permitted; however, stage assignments shall not be skipped or configured in reverse order.

Relay Configuration Result
RL1 = Stage 1, RL2 = Stage 2, RL3 = Stage 3, RL4 = Stage 4 Valid
RL1 = Stage 1, RL2 = Stage 2, RL3 = Stage 2, RL4 = Stage 3 Valid
RL1 = Stage 4, RL2 = Stage 3, RL3 = Stage 2, RL4 = Stage 1 Invalid
RL1 = Stage 1, RL2 = Stage 3, RL3 = Stage 3, RL4 = Stage 4 Invalid

If the configured relay stages do not meet the sequencing requirement, the CCU displays the following validation message:

"Reheat stages for relays should be configured sequentially."

 

Universal Inputs

The SmartNode provides four universal-input terminals. Depending on the selected mapping, a universal input operates as either a thermistor input or an analog input.

Universal Input Default Status Default Mapping Configuration
UI1 Enabled Damper Feedback Fixed
UI2 Disabled Voltage Input Configurable
UI3 Enabled Discharge Air Temperature Fixed
UI4 Enabled Entering Air Temperature Fixed

UI1, UI3, and UI4 are fixed assignments required by this profile. Only UI2 is configurable.

The available mapping options are limited to analog input types.

Analog Input

  • Damper Feedback
  • Voltage Input
  • Current TX (0–10 Amps)
  • Current TX (0–20 Amps)
  • Modulating Reheat Feedback

Mapping Validation for Universal inputs

Modulating Reheat Feedback

When Modulating Reheat is assigned to an analog output, Modulating Reheat Feedback shall also be assigned to a universal input.

For this profile, Modulating Reheat Feedback shall be mapped to UI2.

If the feedback input is not configured, the CCU displays the following validation message:

"Please map the Modulating Reheat Feedback sensor to a universal input to continue."

Duplicate Sensor Mapping

Each sensor function can be assigned to only one universal input.

The following mappings are fixed for this profile:

  • UI1 – Damper Feedback
  • UI3 – Discharge Air Temperature
  • UI4 – Entering Air Temperature

These functions shall not be assigned to UI2.

If a duplicate mapping is detected, the CCU displays the following validation message:

"Each sensor can only be mapped once. Please check your mappings."

If Modulating Reheat Feedback is not assigned when required, the Modulating Reheat Feedback validation message takes precedence over the duplicate sensor validation.

 

|MySense Configuration

Enable MySense is disabled by default.

When enabled, three configurable MySense universal inputs are displayed.

Universal Input Default Status Default Mapping
UI1 Disabled Door/Window Sensor N/C
UI2 Disabled Current TX (0–10 Amps)
UI3 Disabled Generic Alarm N/O

Each input can be enabled independently. The mapping list is displayed after the corresponding input is enabled.

The following mappings are available.

  • Voltage Input
  • Damper Feedback
  • Current TX (0–10 Amps)
  • Current TX (0–20 Amps)
  • Thermistor Input
  • Discharge Air Temperature
  • Entering Air Temperature
  • Generic Alarm N/O
  • Generic Alarm N/C
  • Door/Window Sensor – N/O
  • Door/Window Sensor – N/C
  • Door/Window Sensor – N/O – Title 24
  • Door/Window Sensor – N/C – Title 24
  • Modulating Reheat Feedback

Control Inputs

The following mappings are used by the DAB control sequence.

  • Door/Window Sensor – N/O
  • Door/Window Sensor – N/C
  • Door/Window Sensor – N/O – Title 24
  • Door/Window Sensor – N/C – Title 24

All other mappings are used for monitoring only.

Configure the door/window sensor mapping to match the installed device.

Enable MySense Icon Mode

Enable MySense Icon Mode is displayed only when Enable MySense is enabled.

Default: Disabled

TrueCFM Configuration

The TrueCFM Configuration section defines the airflow limits and damper-position limits used by the DAB profile when Enable TrueCFM Control is enabled.

 

Min CFM IAQ Settings

The Min CFM IAQ setting defines the minimum airflow required to maintain indoor air quality.

Setting Default Range
Min CFM IAQ 100 CFM 0–1500 CFM (10 CFM increments)

K-Factor

The K-Factor defines the airflow coefficient used by the TrueCFM control algorithm.

Setting Default Range
K-Factor 2.0 0.00–10.00 (0.01 increments)

The K-Factor parameter is displayed only when Enable TrueCFM Control is enabled.

 

Damper Position Configuration

The following cooling and heating damper-position limits are available.

Setting Default Range
Min Damper Position Cooling 40% 0–100% (1% increments)
Max Damper Position Cooling 100% 0–100% (1% increments)
Min Damper Position Heating 40% 0–100% (1% increments)
Max Damper Position Heating 100% 0–100% (1% increments)

For information about the airflow calculation and damper control algorithm, refer to DAB Terminal Profile- Damper Position Calculation & Operation.

 

Save the Configuration

After completing all required profile settings, select Save. The SmartNode pairing and DAB profile configuration are then completed.

 

| Operation

Considering there is more than one terminal profile connected to the DAB system profile when the zones are within the deadband the damper positions are managed using the terminal level loop output.

When the temperatures cross the Deadband and zones call for cooling or heating from the system level equipment, the cooling or heating which the system level equipment provides is divided optimally for the zones, to help temperature balance a system without fully closing off zones and creating harmful back pressure on the AHU. This is achieved based on two approaches.

  • Normalization

     
  • Minimum overall Damper Position

Which is based on the DAB profile sequences and uses the aspects like the Zone priority, Damper size, and other tuner parameters for the output calculations.

| Equip Graphics

Equipment graphics is available for all the terminal profiles. It provides a graphical representation of system-level equipment and enables monitoring of key point parameters associated with terminal profiles, along with the alert rings and alert severity legends displayed.

 

| Sequence of Operation

The sequence of operation is completely driven based on Occupancy mode,  Space Current Temperature, the set Cooling and Heating Desired Temperatures, CFM, and Space CO2 & VOC levels.

Let us understand the Sequence of operations based on the occupancy modes, and how the other factors contribute to the sequence of operations during different types of occupancy modes.

| Occupancy Modes

The occupancy mode (Occupied or Unoccupied) shall be determined through a user-adjustable, graphical, seven-day schedule with a holiday schedule, alongside the configurable autoaway and forced occupied options (external schedule influencers) for optimized controls and enhanced energy savings.

Based on the above aspects factoring into the occupancy the following can be the possible applicable occupancy modes:

    • Pre- Conditioning
    • Occupied
    • Unoccupied
    • Auto-Away
    • Forced Occupied

| Sequence of Operation During Pre-Conditioning

Pre-conditioning is a state just before the building enters the scheduled occupancy. It starts at more like the unoccupied state, the desired temperatures drift to unoccupied setbacks.

The preconditioning uses an algorithm to start the conditioning before the building schedule, from the heating side or cooling side, to bring the building to an optimum level ( within the occupied heating & cooling desired temperatures) exactly at the time of occupancy start.

The zones would operate as shown below to accommodate the preconditioning from the system equipment.

A coolingPreconditioningRate and heatingPreconditiningRate tuners defaulted to 15 minutes, are used alongside the occupied heating/cooling desired temperature breach to determine when the pre-conditioning should start.

Example Calculation:

When,

    • The heating & cooling desired temperatures are 70F and 74F for the building,
    • The current temperature is 76F (Average of zone temperatures),
    • 8:00 AM is the time the building is scheduled to be occupied.

Then the preconditioning start time is calculated as follows:

Cooling Desired Temperature Breach= 76-74=2F

Preconditioning duration= coolingPreconditioningRate (mins) * Cooling Desired Temperature Breach

                                        = 15*2

                                        = 30 mins

The preconditioning starts 30 minutes before the building is scheduled to be occupied, which is = 7:30 AM

During Warm-up:

    • If the space temperature is below the occupied heating desired temperature, the space utilizes the warm-up via HeatingLoopOutput as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The Damper remains at a minimum

The HeatingLoopOutput is mapped to the Damper position actuator

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

    • The CO2 and IAQ loops are disabled. (If configured for)
    • The CFM loop is disabled. (If configured for)

During Pre-cooling:

    • If the space temperature is below the occupied cooling desired temperature, the space utilizes the morning pre-cooling via CoolingLoopOutput, as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The Damper position moves to the minimum position

  • The CO2 and IAQ loops are disabled. (If configured for)

| Sequence of Operation During Occupied

At all occupied times: (based on a set schedule)

  • The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.

During Deadband:

During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.

Configuration Damper Operation
If only the zone temperature-based configuration is enabled.

The damper shall be at its minimum position and the reheat valve will remain closed.

The Dmaper minimum is decided based on the last known conditioning,

  • If the zone reaches deadband from the heating side the Heating Damper Minimum is considered. 
  • If the zone reaches deadband from the Cooling side the Cooling Damper Minimum is considered. 
If zone Temperature & CO2-based configuration is enabled.

The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & VOC-based configuration is enabled.

The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & CFM-based configuration is enabled. The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation
If zone Temperature,  IAQ(CO2 & VOC) & CFM-based configuration is enabled. The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

 

During Heating:

    • When the space current temperature falls below the HeatingDesiredTemperature the HeatingLoopOutput is enabled as below as below.
If System Equipment is in Cooling Mode If System Equipment in Heating Mode

The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90)

Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

    • The CFM loop is disabled. (If configured for)

During Cooling:

    • When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled, as below
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The CFM loop is enabled  (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The Damper position moves to the minimum position, not allowing further hot air into the room.

The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm)

Note: The fan runs wherever the zone is occupied and when the reheat is enabled.

| Sequence of Operation During Autoaway

    • The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
    • The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.

During Deadband:

    • CoolingLoopOutput, HeatingLoopOutput, CFM LoopOutput, CO2 and IAQ Loop Output, and Reheat Stages are disabled.

During Heating:

    • When the space current temperature falls below the heating autoaway setback temperature, the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90)

Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

    • The CO2 and IAQ loops are disabled. (If configured for)
    • The CFM loop is disabled. (If configured for)

During Cooling:

    • When the space current is above the cooling autoaway setback temperature, the CoolingLoopOutput is enabled, as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The CFM loop is enabled  (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The Damper position moves to the minimum position, not allowing further hot air into the room.

The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm)

    • The CO2 and IAQ loops are disabled. (If configured for)

Note: The fan runs wherever the zone is occupied and when the reheat is enabled.

| Sequence of Operation During Unoccupied

    • The range of Heating Desired Temperature and Cooling Desired Temperature drifts further away.
    • The device maintains a space temperature within the newly set Heating Desired Temperature and Cooling Desired Temperature Range.

During Deadband:

During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.

Configuration Damper Operation
If only the zone temperature-based configuration is enabled.

The damper shall be at its minimum position and the reheat valve will remain closed.

The Dmaper minimum is decided based on the last known conditioning,

  • If the zone reaches deadband from the heating side the Heating Damper Minimum is considered. 
  • If the zone reaches deadband from the Cooling side the Cooling Damper Minimum is considered. 
If zone Temperature & CO2-based configuration is enabled.

The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & VOC-based configuration is enabled.

The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & CFM-based configuration is enabled. The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation
If zone Temperature,  IAQ(CO2 & VOC) & CFM-based configuration is enabled. The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

During Heating:

    • When the space's current temperature falls below the heating unoccupied setback temperature, the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90)

Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

    • The CO2 and IAQ loops are disabled. (If configured for)
    • The CFM loop is disabled. (If configured for)

During Cooling:

    • When the space current temperature is above the cooling unoccupied setback temperature, the CoolingLoopOutput is enabled, as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The CFM loop is enabled  (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The Damper position moves to the minimum position, not allowing further hot air into the room.

The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm)

    • The CO2 and IAQ loops are disabled. (If configured for)

Note: The fan runs wherever the zone is occupied and when the reheat is enabled.

| Sequence of Operation During Forced Occupied

    • The device maintains a space temperature within the Heating Desired Temperature and Cooling Desired Temperature Range.

During Deadband:

During deadband, the damper operation is influenced, based on the configuration of the profile, as follows.

Configuration Damper Operation
If only the zone temperature-based configuration is enabled.

The damper shall be at its minimum position and the reheat valve will remain closed.

The Dmaper minimum is decided based on the last known conditioning,

  • If the zone reaches deadband from the heating side the Heating Damper Minimum is considered. 
  • If the zone reaches deadband from the Cooling side the Cooling Damper Minimum is considered. 
If zone Temperature & CO2-based configuration is enabled.

The Damper position is driven based on the Zone CO2 levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & VOC-based configuration is enabled.

The Damper position is driven based on the Zone VOC levels. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

Note: It is possible and likely that temperature control will not be as good when IAQ controls override the damper position. This is indicated by the iaqOverridingDamper being set to true.

If zone Temperature & CFM-based configuration is enabled. The Damper position is driven based on the min-max CFM set. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation
If zone Temperature,  IAQ(CO2 & VOC) & CFM-based configuration is enabled. The Damper position is driven based on Temperaue, IAQ, and CFM. For more information on the actual calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

During Heating:

    • When the space current temperature falls below the Heating Desired Temperature the HeatingLoopOutput is enabled as below.
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The Damper remains at a minimum from 0% - 50% of the Heating Loop Output, till a maximum Discharge Air Temperature (DAT) is reached, defined by the reheatZoneMaxDischargeTemp tuner (90)

Then the Reheat loop output is enabled, based on the DAT set point and actual DAT for the loop output calculation.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The HeatingLoopOutput is mapped to the Damper position actuator and further to modulating reheat or reheat stages.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

    • The CO2 and IAQ loops are disabled. (If configured for)
    • The CFM loop is disabled. (If configured for)

During Cooling:

    • When the space current temperature is above the Cooling Desired Temperature the CoolingLoopOutput is enabled as below,
If System Equipment in Cooling Mode If System Equipment in Heating Mode

The CoolingLoopOutput is mapped to the Damper position actuator for the damper position between the min-max damper position cooling.

For more information on the Damper position calculation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The CFM loop is enabled  (If configured for) which is mapped to the Damper position actuator for more information on the CFM influence on the operation refer to DAB Terminal Profile- Damper Position Calculation & Operation

The Damper position moves to the minimum position, not allowing further hot air into the room.

The Active airflow setpoint will be no higher than the minimum endpoint (minimum Cfm)

  • The CO2 and IAQ loops are disabled. (If configured for)

Note: The fan runs wherever the zone is occupied and when the reheat is enabled.

| Sequence of Operation During Emergency Conditioning

When zone limits are violated, and the recorded temperature is within the zone limit plus leeway the conditioning will happen in the direction of zone load.

| Sequence of Operation During Zone Temp Dead

And, When the zone temperature breaches the zone limits, beyond the leeway limits all the following loops are disabled:

    • CoolingLoopOutput
    • HeatingLoopOutput
    • Reheat Stages
    • FanLoopOutput
    • CO2 & IAQ LoopOutput
    • CFM LoopOutput

| Control Mode Summary

Modes & 

Operation

Pre-Conditioning Occupied AutoAway Unoccupied Forced Occupied
Auto

HeatingLoopOutput FanLoopOutput

CoolingLoopOutput

FanloopOutput

CFMLoopOutput

HeatingLoopOutput FanLoopOutput

CoolingLoopOutput

FanloopOutput

CFMLoopOutput

CO2LoopOutput

IAQLoopOutput

HeatingLoopOutput FanLoopOutput

CoolingLoopOutput

FanloopOutput

HeatingLoopOutput FanLoopOutput

CoolingLoopOutput

FanloopOutput

HeatingLoopOutput FanLoopOutput

CoolingLoopOutput

FanloopOutput

Heat Only

HeatingLoopOutput FanLoopOutput

HeatingLoopOutput FanLoopOutput

CO2LoopOutput

IAQLoopOutput

HeatingLoopOutput FanLoopOutput

HeatingLoopOutput FanLoopOutput

HeatingLoopOutput FanLoopOutput

CO2LoopOutput

IAQLoopOutput

Cool Only

CoolingLoopOutput

FanLoopOutput

CFMLoopOutout

CoolingLoopOutput

FanloopOutput

CFMLoopOutput

CO2LoopOutput

IAQLoopOutput

CoolingLoopOutput

FanLoopOutput

CoolingLoopOutput

FanLoopOutput

CoolingLoopOutput

FanLoopOutput

CO2LoopOutput

IAQLoopOutput

Off

All Loops Deactivated

 