Problem:
Currently, the SmartNode cannot control a floating point damper or valve actuator with the on-board relay outputs. There are cases when retrofitting a floating point actuator does not make sense, so using a SmartNode for control would be a requirement.
Solution:
Using a SmartNode we can accomplish floating point control by using an analog to floating point signal interface module. The module converts an analog signal into two relay contact outputs. One relay controls UP (increase), and the other DOWN (decrease) depending on the actuator configuration.
How does it work ?:
For this example, we are going to work within a 0-10vdc range.
0-4 VDC signal:
As the analog input signal decreases below 4 volts, relay 2 (wired NC) energizes. This relay is the counter-clockwise or down signal output. Once the condition is satisfied and the signal increases beyond 4 volts, the relay energizes and contacts open.
4-6 VDC signal:
Between the voltage ranges, "floating point” control can be obtained, and no relay action takes place. The output on both relays 1 and 2 is open.
6-10 VDC signal:
When the analog input signal is above 6 volts, relay 1 (wired NO) energizes. This is the clockwise or up signal output. Once the condition is satisfied and the signal falls below 6 volts, the relay de-energizes and contacts open.
In addition, in the event of a power loss, the AFP's output relays will be open, and no signal will be generated. The actuator will remain at the last commanded position unless it's a "spring return."
Result:
- Floating point control can be used with either DAB or VAV applications.
- Using an AFP board with a SmartNode presents a viable option to keep existing floating point actuators.
Notes:
75F designs with an ACI analog input to floating point output module, model number AFP (version 1) and provides them as part of our product when required.