Temperature Modes define how HyperStat Split determines, displays, and adjusts temperature setpoints. The available temperature adjustment behavior depends on the configured Temperature Mode. 

This article describes the temperature-control behavior and adjustment logic for each supported mode. For information about configuring Temperature Modes, refer to Temperature Modes: Overview.

 

| Supported temperature modes

HyperStat Split supports the following Temperature Modes:

No. Temperature Mode Behavior

1

Dual Setpoint Fixed Deadband Maintains a fixed relationship between the Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT).

2

Dual Setpoint Variable Deadband Allows HDT and CDT to be adjusted independently while maintaining the minimum required deadband.

3

Single Setpoint Provides a single user-adjustable temperature setpoint and maintains the corresponding HDT and CDT.

4

Setpoint Offset Allows the user to adjust temperature relative to the configured baseline comfort setting.

 

| Temperature Adjustment Limits

HyperStat Split follows the temperature adjustment limits configured in the system/CCU. 

For details about configuring temperature adjustment limits, refer to Temperature Modes: Overview.

 

| Dual Setpoint Fixed Deadband

In Dual Setpoint Fixed Deadband mode, the Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT) maintain a fixed deadband. When the user adjusts one setpoint, the other setpoint adjusts as required to maintain the configured deadband, subject to the applicable user limits.

Device Display and Temperature Adjustment

To access and adjust the temperature on the HyperStat Split:

  • Press Button 2 (+) or Button 3 (−) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.

  • Use Button 2 (+) and Button 3 (−) to increase or decrease the temperature; the display updates to reflect the selected temperature.

Adjustment Range and Formula

The available temperature adjustment on the HyperStat Split is determined by the configured Heating and Cooling User Limits and the applicable deadbands.

The heating and cooling setpoints maintain the following relationship:

CDT − HDT = Heating Deadband + Cooling Deadband

Example : 

Initial State

Parameter Value
HDT 72°F
CDT 76°F
Deadband 4°F

User action: Adjust HDT from 72°F to 70°F

Result

Parameter Value
HDT 70°F
CDT 74°F
Deadband 4°F

Therefore, when one setpoint is adjusted, the other setpoint is adjusted as needed to maintain the 4°F deadband while remaining within the configured user limits.

For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Fixed Deadband.

 

| Dual Setpoint Variable Deadband

In Dual Setpoint Variable Deadband mode, HDT and CDT can be adjusted independently while maintaining the minimum required deadband. If an adjustment would reduce the difference between HDT and CDT below the configured minimum, the other setpoint adjusts to maintain the required minimum deadband.

Device Display and Temperature Adjustment

To access and adjust the temperature on the HyperStat Split:

  • Press Button 2 (+) or Button 3 (−) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.

  • Press Button 1 to switch between Heating and Cooling temperature adjustment.
  • Use Button 2 (+) and Button 3 (−) to increase or decrease the temperature; the display updates to reflect the selected temperature.

Adjustment Range and Formula

The available temperature adjustment on the HyperStat Split is determined by the configured Heating and Cooling User Limits and the applicable deadbands.

The heating and cooling setpoints maintain the following relationship:

CDT − HDT ≥ Heating Deadband (HDB) + Cooling Deadband (CDB)

The user can adjust HDT and CDT independently within the configured user limits. If an adjustment would cause the setpoints to violate the minimum required deadband, the other setpoint automatically adjusts to maintain the required deadband.

Example : 

Initial State

Parameter Value
HDT 67°F
CDT 77°F
Deadband 4°F

Scenario 1: Decreasing CDT

User action: Decrease CDT from 77°F to 72°F.

Result:

Parameter Value
HDT 67°F
CDT 72°F
Deadband 4°F

The HDT remains unchanged because the minimum required deadband is maintained.

Scenario 2: Increasing HDT

User action: Increase HDT from 67°F to 70°F.

Result:

Parameter Value
HDT 70°F
CDT 74°F
Deadband 4°F

The CDT automatically adjusts from 72°F to 74°F to maintain the minimum required deadband.

For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Variable Deadband.

 

| Single Setpoint

In Single Setpoint mode, the user adjusts a single temperature setpoint. The system uses the configured fixed deadband to determine the corresponding HDT and CDT. When the Single Setpoint changes, HDT and CDT adjust accordingly while maintaining the configured deadband.

Device Display and Temperature Adjustment

To access and adjust the temperature on the HyperStat Split:

  • Press Button 2 (+) or Button 3 (−) to access the temperature screen, which displays the Single Setpoint temperature.

  • Use Button 2 (+) and Button 3 (−) to increase or decrease the temperature; the display updates to reflect the temperature.

Adjustment Range and Formula

The available temperature adjustment on the HyperStat Split is determined by the configured Heating and Cooling User Limits and applicable deadbands. 

In Single Setpoint mode, the user adjusts only the Single Setpoint. The Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT) are calculated based on the Single Setpoint and configured deadbands.

The Single Setpoint maintains the following relationship:

Single Setpoint = HDT + HDB

Single Setpoint = CDT − CDB

When the Single Setpoint is adjusted, the system automatically recalculates the HDT and CDT to maintain the configured fixed deadband.

Example : 

Initial State

Parameter Value
HDT* 70°F
CDT* 74°F
Single Setpoint 72°F
Deadband 4°F

User action: Increase the Single Setpoint from 72°F to 74°F

Result

Parameter Value
HDT* 72°F
CDT* 76°F
Single Setpoint 74°F
Deadband 4°F

Note : HDT and CDT are calculated values and are not displayed on the HyperStat Split in Single Setpoint mode.

The Single Setpoint is the user-adjustable value displayed on the device. The system uses it to calculate the corresponding HDT and CDT while maintaining the configured deadband.

For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Single Setpoint.

 

| Setpoint Offset

In Setpoint Offset mode, the user adjusts the temperature relative to the baseline comfort setting using a Setpoint Offset value. An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.

Device Display and Temperature Adjustment

When Setpoint Offset mode is configured, the HyperStat Split home screen displays the current Setpoint Offset value and its available range.

  • Use Button 2 (+) and Button 3 (−) to increase or decrease the Setpoint Offset value. The displayed offset updates accordingly.

Adjustment Range and Formula

The available Setpoint Offset range on the HyperStat Split is determined by the configured Heating and Cooling User Limits and Heating and Cooling Deadbands.

The Setpoint Offset maintains the following relationship:

Setpoint Offset = HDT + HDB

Setpoint Offset = CDT − CDB

An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.

For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Setpoint Offset. 