CCU Master Control is a building-level temperature management feature that defines the building setpoint temperature and the upper and lower temperature limits used for building breach conditioning. When a Central Control Unit (CCU) is commissioned, the system automatically applies these values based on predefined energy-saving algorithms, establishing the baseline operating parameters for the entire building. These settings create a common temperature framework for all zones associated with the CCU.

All zones paired with the CCU inherit the temperature boundaries defined in Master Control, ensuring that local temperature adjustments remain aligned with the building's energy-efficiency and comfort strategy. As a result, users cannot adjust zone desired temperatures beyond the configured limits through the Portal, mobile applications, or other smart devices. This centralized control prevents individual zones from operating outside the approved building temperature range while maintaining consistent and efficient building wide operation.

image.png

| Master Control Capabilities

Building-Level Temperature Control

  • Defines the building's primary temperature setpoint.
  • Establishes upper and lower temperature thresholds for building breach conditioning.
  • Provides a common temperature framework for all zones associated with the CCU.

Automatic Configuration

  • When a CCU is commissioned, the system automatically assigns building setpoints and breach conditioning temperatures based on predefined energy-saving algorithms.
  • These values serve as the baseline operating parameters for the building.

Zone Temperature Enforcement

  • All zones paired with the CCU inherit the temperature boundaries defined in Master Control.
  • Users cannot adjust zone desired temperatures beyond these configured limits through the Portal, mobile applications, or other smart devices.
  • This prevents individual zones from operating outside the building's approved temperature range.

| Access CCU Master Control (Temperature Limits)

To access CCU Master Control:

  • Click the Settings icon in the upper-right corner of the dashboard.
image.png
  • On the Floor Layout page, select the Settings tab.
  • The Settings page is displayed.
  • Click Installer Operations from the left navigation pane.
  • The Installer Operations page is displayed.
  • Scroll to the Building section and locate Temperature Limits.
  • Click the temperature limits slider to modify the building temperature limits.
  • The Temperature Limits window is displayed. Configure the required settings under Building Limits, User Limits, and Deadbands and Unoccupied Zone Setback. 
  • Click the dropdown arrow corresponding to the setting you want to modify.
  • A list of all available values within the allowed configuration range is displayed.
image.png
  • Select the required value from the dropdown list. Repeat the process for any additional settings that require modification.
  • Click Set to save the updated temperature limit configuration.
  • If any existing zone schedule contains heating or cooling setpoints that fall outside the newly configured temperature limits, the Schedule Errors dialog is displayed.
  • Review the affected zones, schedules, and setpoint values listed in the error message. Click OKAY to close the dialog.
  • Modify the affected zone schedules or adjust the temperature limits so that all heating and cooling setpoints fall within the allowed range.
  • Click Set again to save the updated configuration.
  • A confirmation message, "Building limits has been successfully updated", is displayed, indicating that the temperature limit configuration has been saved successfully.

 

| Master Control (Temperature Limits)


Building Limits

The Building Limits section defines the allowable temperature boundaries for the building and the relationship between building-level and zone-level temperature settings. These limits are applied to all zones that follow the building temperature settings and help ensure consistent building-wide temperature control.

SettingDescription
Building Limit Min

Specifies the lowest allowable building temperature. The building setpoint and associated zone temperatures cannot be configured below this value. The configurable range is 32°F to 140°F.

Building Limit Max

Specifies the highest allowable building temperature. The building setpoint and associated zone temperatures cannot be configured above this value. The configurable range is 32°F to 140°F.

Building to Zone Differential
Defines the maximum allowable deviation between the building setpoint and zone setpoints. Configurable from 0°F to 20°F. A value of 0°F requires zones to match the building setpoint exactly, while larger values allow greater temperature flexibility. This ensures that zones following building temperature settings remain within an acceptable range of the building-level temperature while preserving occupant comfort and system efficiency.

Note: The values configured in the Building Limits section apply to all zones that follow building temperature settings. Building Limit Min and Building Limit Max can only be configured within the range of 32°F to 140°F, establishing the operating boundaries for building and zone temperature control.

Note: The Building to Zone Differential can be configured between 0°F and 20°F.

User Limits

The User Limits section defines the temperature range within which users can adjust zone setpoints. These limits control the minimum and maximum heating and cooling temperatures that can be selected from the Portal, mobile applications, and other supported devices.

Note: All User Limit values must be configured within the range of 50°F to 100°F.

SettingDescription
Heating User Limit Min

Defines the lowest heating setpoint that users can select for a zone. Users cannot decrease the heating setpoint below this value.

Heating User Limit Max

Defines the highest heating setpoint that users can select for a zone. Users cannot increase the heating setpoint above this value.

Cooling User Limit Min

Defines the lowest cooling setpoint that users can select for a zone. Users cannot decrease the cooling setpoint below this value.

Cooling User Limit Max

Defines the highest cooling setpoint that users can select for a zone. Users cannot increase the cooling setpoint above this value.

 

Deadbands

The Deadbands section defines the temperature differential between heating and cooling operation to prevent simultaneous heating and cooling and reduce unnecessary equipment cycling.

Note: Deadband values can only be configured between 0.5°F and 10°F.

SettingDescription
Heating Deadband

Defines the temperature offset below the setpoint before heating is allowed to operate. A larger deadband can reduce equipment cycling and improve energy efficiency.

Cooling Deadband

Defines the temperature offset above the setpoint before cooling is allowed to operate. This helps maintain stable operation while minimizing unnecessary cooling cycles.

 

Unoccupied Zone Setback

The Unoccupied Zone Setback section defines how much the occupied temperature setpoint can be adjusted during unoccupied periods to conserve energy.

SettingDescription
Setback

Specifies the number of degrees by which heating and cooling setpoints can be relaxed when a zone is unoccupied. Increasing the setback value can improve energy savings while the space is not in use.

Note: The values configured in the User Limits, Deadbands, and Unoccupied Zone Setback sections apply to all zones that are configured to follow the building temperature settings. These settings help balance occupant comfort, operational consistency, and energy efficiency across the building.