| Overview
Portal Reconfiguration feature provides a dedicated section for managing MyStat v2 device settings in both the Heatmap Internal Portal and Facilisight Portal. This section allows users to view and modify supported MyStat v2 configuration settings directly from the portal without requiring separate updates in the CCU.
Configuration changes are synchronized automatically between the portal and the CCU. When a setting is updated in the Reconfiguration section, the corresponding configuration is applied to the associated CCU. Similarly, any supported changes made in the CCU are automatically reflected in the portal, ensuring that both systems remain synchronized and display the latest configuration values.
This bidirectional synchronization streamlines device management, improves configuration consistency, and provides a centralized interface for managing MyStat v2 settings such as relay mappings, temperature offsets, display options, access controls, and other supported configuration parameters.
| Purpose of Portal Reconfiguration
- Provide a dedicated interface in the Heatmap Internal Portal and Facilisight Portal for managing MyStat v2 configuration settings.
- Allow users to view and update supported MyStat v2 settings without accessing the CCU directly.
- Maintain automatic bidirectional synchronization between the portals and the CCU.
- Ensure that configuration changes made in the portal are automatically applied to the associated CCU.
- Reflect configuration changes made in the CCU automatically within the portal.
- Eliminate the need for duplicate configuration updates across multiple interfaces.
- Improve configuration consistency by keeping portal and CCU settings synchronized.
- Simplify device management through a centralized configuration experience.
- Reduce manual configuration effort and the risk of configuration mismatches.
- Provide a single source of truth for supported MyStat v2 configuration settings and mappings.
| Access the MyStat v2 Configuration Page in CCU
- From the CCU Home screen, tap the Settings (⚙️) icon in the upper-right corner.
- On the Floor Layout page, locate and select the MyStat v2 device.
- The MyStat v2 Configuration page opens, where you can view and modify the device configuration settings.
| Access the MyStat v2 Reconfiguration Page in Facilisight Portal
- Log in to the Facilisight Portal.
- From the left navigation pane, select the required Organization/Site.
- The Heatmap page opens and displays the site overview.
- Navigate to the floor containing the target device, then select the desired Zone where the MyStat v2 device is installed.
- The selected zone opens and displays the zone graphic. Select the MyStat v2 device to open the device details page, where you can view equipment graphics, monitoring parameters, equipment parameters, and the Reconfiguration section.
- Scroll down to the Reconfiguration section to view and modify the available MyStat v2 configuration settings.
| Access the MyStat v2 Reconfiguration Page in Internal Portal
- Log in to the Internal Portal.
- From the Site Dashboards page, select the required Site from the Select Site drop-down menu in the upper-left corner.
- The Heatmap page opens and displays the site overview.
- Navigate to the floor containing the target device, then select the desired Zone where the MyStat v2 device is installed.
- The selected zone opens and displays the zone graphic. Select the MyStat v2 device to open the device details page, where you can view equipment graphics, monitoring parameters, equipment parameters, and the Reconfiguration section.
- Scroll down to the Reconfiguration section to view and modify the available MyStat v2 configuration settings.
| How to Reconfigure MyStat v2 in the Portals
The Reconfiguration page enables you to manage MyStat v2 settings directly from the Heatmap Facilisight Portal or Internal Portal. Any changes made to configuration settings, such as toggle switches, relay mappings, sensor mappings, temperature offsets, or other supported parameters, are automatically synchronized with the associated CCU. This bidirectional synchronization ensures that configuration changes made in either the portal or the CCU are reflected across both interfaces, helping maintain consistent and up-to-date device settings.
Example:
Update a MyStat v2 Configuration Setting
The following example demonstrates how to update a mapping and change a device setting from the Reconfiguration page.
- Review the existing MyStat v2 configuration settings displayed on the Reconfiguration page.
- Under the Mapping section, change the Cooling Water Valve mapping to Fan Enable.
- Under Miscellaneous Settings, toggle Enable Icon-Only Mode to Off.
- In the Reason for change field, enter a justification for the update (for example, "Testing purpose").
- Click Save to apply the changes.
- A confirmation message appears indicating that the configuration changes have been successfully saved.
Note: After the changes are saved, the updated configuration is automatically synchronized with the associated CCU. The new mapping and setting values are reflected in both the portal and the CCU.
- Open the CCU and navigate to the desired MyStat v2 Configuration page.
- Verify that the relay mapping has been updated from Cooling Water Valve to Fan Enable.
- Verify that the Enable Icon-Only Mode setting has been updated to Off. The updated settings confirm that the configuration changes made in the portal have been successfully synchronized with the CCU.
Note: Changes made from the Reconfiguration page in the Heatmap Internal Portal or Facilisight Portal are automatically synchronized with the associated CCU. Similarly, any supported configuration changes made directly on the CCU are reflected in the portals after synchronization. This bidirectional synchronization helps ensure configuration consistency across all interfaces and eliminates the need to manually update settings in multiple locations.