| Overview

CPM architecture is Haystack 4 compliant i.e. tags, point, equip definition, and ontology are as per Haystack Standard.

CPM queries the tags to identify equipment and devices which are associated with it.

It is expected from all our users to utilize the below-mentioned tags to define equip and point:

EQUIPS

Sr. No.EquipTags
1Water Cooled Chillerchiller, waterCooling
2Air Cooled Chillerchiller, airCooling
3Cooling TowercoolingTower
4Cooling Tower with 2 FancoolingTower, cell: 2
5Cooling Tower with 4 FancoolingTower, cell: 4
6Condenser Boilerboiler, condenser or condensate
7Steam Boilerboiler, steam
8Pumppump
9Chilled Water Supply Header Pipechilled, header, pipe, supply or entering
10Chilled Water Return Header Pipechilled, header, pipe, return or leaving
11Hot Water Supply Header Pipehot, header, pipe, supply or entering
12Hot Water Return Header Pipehot, header, pipe, return or leaving
13Condenser Water Supply Header Pipecondenser, header, pipe, supply or entering
14Condenser Water Return Header Pipecondenser, header, pipe, return or leaving
15Supply header pipeheader, pipe, supply or entering
16Return header pipeheader, pipe, return or leaving
17Building Load Hotbuilding, hot
18Building Load Chilledbuilding, chilled
19BTU Meterthermal, meter

 

SUB-EQUIPS

Sr. No.Sub-equipTags
1Chilled water entering pipechilled, entering, pipe
2Chilled water leaving pipechilled, leaving, pipe
3Hot water entering pipehot, entering, pipe
4Hot water leaving pipehot, leaving, pipe
5Condenser Water entering pipecondenser, entering, pipe
6Condenser Water leaving pipecondenser, leaving, pipe

 

DEVICES

Sr. No.DevicesTags
1flow meterflow, meter
2valve actuatorvalve, cmd or sensor
3temperature sensorsensor, temp
4well temperature sensorwell, sensor, temp
5flow switchflow, switch
6pressure sensorpressure, sensor