| Overview
Freeze Stat is a safety feature designed to protect hydronic coils in unit ventilators from potential freezing conditions that could damage the coil or cause it to burst. The feature is supported in the HyperStat Split (HSS) and MyStat Split (MSS) hydronic unit ventilator profiles.
The feature supports two configuration options:
- Freezestat N/O (Normally Open)
- Freezestat N/C (Normally Closed).
The appropriate option can be mapped through the HyperLite or MySense UI or Connect Module UI for MyStat Split configurations, as applicable.
When a freeze stat condition is detected, the system overrides normal equipment operation and applies the required protective actions. These include stopping the fans, closing the outside air damper, and driving the hot water valve to 100% open, regardless of whether the valve is controlled through an analog or relay mapping. Exhaust and return fans are also turned off.
Freeze Stat protection takes precedence over normal user intent and other applicable control conditions according to the defined fan-control priority. An alert is triggered whenever the freeze stat is active.
| How It Works
- Configuration: Select the appropriate Freeze Stat type (N/O or N/C) and map the input through the supported configuration interface.
- Condition Detection: The system monitors the configured freeze stat input and detects when the freeze stat becomes active.
- Protective Actions: When activated, the system stops the fans, closes the outside air damper, and drives the water valve to 100% open. This valve action applies across heating, cooling, and deadband conditions and supports both analog and relay mappings.
- Fan-Control Override: Freeze Stat overrides lower-priority fan-control requests, ensuring that normal user intent or other lower-priority conditions cannot enable the fans while freeze protection is active.
- Alerting: The system triggers an alert when the freeze stat is active to notify users of the protective condition.
- Timer Handling: Stage-up and stage-down timers do not apply during Freeze Stat operation.
| Control Behaviour
When Freeze Stat is active, the following protective actions apply:
- Supply and exhaust fans: Stop all applicable fans, including return and exhaust fans.
- Outside air damper: Close the damper. If the outside air output is already open, drive it to its configured minimum position, as specified by the applicable control requirement.
- Water valve: Drive the valve to 100% open, regardless of the supply water temperature (SWT) operating range or whether the valve is mapped to an analog output or relay.
- Auxiliary fan requests: Override lower-priority requests to operate the fans.
- Alert: Trigger an alert while the freeze stat is active.
- Stage timers: Bypass stage-up and stage-down timers during the protective response.
| Fan-Control Priority
When multiple conditions or user requests affect fan operation, the system follows this priority order, from highest to lowest:
- Emergency Shut Off
- Freeze Stat
- Door/Window T24
- Door/Window
- Condensate Detection
- User Intent
A higher-priority condition overrides lower-priority requests. Therefore, when Freeze Stat is active, fan operation follows the Freeze Stat protective requirements unless a higher-priority Emergency Shut Off condition applies.
| Applicable Profiles
- HyperStat Split (HSS) – 2-Pipe Unit Ventilator
- HyperStat Split (HSS) – 4-Pipe Unit Ventilator
- MyStat Split (MSS) – 2-Pipe Unit Ventilator
- MyStat Split (MSS) – 4-Pipe Unit Ventilator
| Freeze Stat Water Valve Behaviour
| Operating condition | Supply water temperature (SWT) | Expected valve behaviour |
|---|---|---|
| Heating | SWT > 85°F | Drive valve to 100% open |
| Deadband | 65°F < SWT < 85°F | Drive valve to 100% open |
| Cooling | SWT < 65°F | Drive valve to 100% open |