| Overview
The A2L Refrigerant Leak Detection feature enables supported HVAC system profiles to detect a potential refrigerant leak using a connected thermistor input and automatically transition the system into a protective operating state.
A2L refrigerants, such as R-454B, R-32, and HFO-1234yf, are classified as mildly flammable refrigerants. This feature introduces refrigerant leak detection and a dedicated fan-control response to help mitigate risks associated with a detected leak.
When an A2L refrigerant leak is detected, the system disables all heating and cooling stages and operates the fan according to the configured A2L Fan Speed tuner.
The A2L control state takes precedence over other applicable control states, including Emergency Shutoff, Keycard Auto-Away, and condensation detection.
| Scope and Applicability
Supported System Profiles
A2L Refrigerant Leak Detection is supported in the following four system profiles:
- VAV Staged RTU with VFD Fan
- VAV Fully Modulating AHU
- DAB Staged RTU with VFD Fan
- DAB Fully Modulating AHU
Supported Devices
A2L control indication is available in the device statistics and Nodes views for:
- Hyperstat Split (Conventional Package Unit)
- MyStat Split (Conventional Package Unit)
- MYstat (Conventional Package Unit & heat Pump Unit)
Input Configuration
The A2L refrigerant leak detection input must be mapped to either Thermistor 1 or Thermistor 2.
The input can be configured using one of the following options:
- A2L Refrigerant Leak NO — Normally Open
- A2L Refrigerant Leak NC — Normally Closed
The selected configuration determines how the input state is interpreted. The applicable wiring and input-state behaviour must be verified against the device configuration and hardware requirements.
Note: The configuration options for the A2L Refrigerant Leak are also made available on the Terminal Standalone Profiles mentioned above.
| Leak Detection
The system monitors the configured thermistor input to determine whether an A2L refrigerant leak condition is present.
A refrigerant leak is detected when the thermistor value falls below 10,000 Ohms, according to the configured input evaluation logic.
For NO NC type Leak Detection
| Type | Resistance Value | State |
| NO | Below 10K Ohms | Fault |
| NO | Above 10K Ohms | Normal |
| NC | Above 10K Ohms | Fault |
| NC | Below 10K Ohms | Normal |
When this condition is detected, the system:
| Equipment Status
A new equipment status, A2L Refrigerant Leak Detected, is introduced to indicate that the system has detected a potential refrigerant leak and has entered the A2L protective operating state.
This status provides visibility into the active fault condition and helps users identify why normal heating and cooling operation has been suspended.
| Heating and Cooling Shutdown
While the A2L refrigerant leak condition is active:
- All heating stages are turned off.
- All cooling stages are turned off.
- Normal heating and cooling demands are overridden.
- Only the fan is permitted to operate, subject to the configured A2L fan-control logic.
The system must remain in the A2L protective state for as long as the leak condition is active.
| Fan Control During an A2L Leak
A2L Fan Speed Tuner
A new configurable parameter, A2L Fan Speed, is introduced to determine the fan operating level during an A2L refrigerant leak condition.
The tuner value is expressed as a percentage and determines which fan stages are activated, based on the applicable system configuration.
| System-Level Fan Operation
For system-level configurations in which Fan Low, Fan Medium, and Fan High are available:
| A2L Fan Speed tuner | Fan operation |
|---|---|
| Above 65% | Fan Low, Fan Medium, and Fan High are turned ON |
The behaviour for values at or below 65% must follow the defined system-level control logic.
| Standalone Fan Operation
For standalone configurations in which only Fan Low and Fan High are available:
| A2L Fan Speed tuner | Fan operation |
|---|---|
| Above 50% | Fan Low and Fan High are turned ON |
| Below 50% | Only Fan Low is turned ON |
The behaviour at exactly 50% must be confirmed in the implementation requirements.
| Post-Fault Fan Operation
When the A2L refrigerant leak condition is resolved, the system continues operating the fan stage that was active during the fault condition for the configured post-conditioning duration.
A tuner, Min Fan Running Post Conditioning, defines the minimum duration, in minutes, for which the fan continues to run after the A2L fault status clears.
During this period:
- The fan continues to operate according to the defined post-fault behaviour.
- Heating and cooling operation must remain subject to the applicable control and safety logic.
- The configured duration determines when the post-conditioning fan operation can end.
The exact interaction between the post-conditioning timer and any newly occurring fault or higher-priority safety condition must follow the implemented control logic.
| Control Priority
A2L control has the highest precedence among the specified operating states.
When an A2L refrigerant leak is detected, its control actions override the following:
- Emergency Shutoff
- Keycard Auto-Away
- Condensation Detection
- Other applicable system-profile and standalone operating states
While A2L control is active, lower-priority states must not re-enable heating or cooling or otherwise override the A2L protective fan-control behaviour.
| Visibility Via Equip Graphics & Widgets
The A2L Refrigerant leakage detection point is made available for better visibility in the Equip Grahics for the System & Standalone Profiles.