| Overview
Temperature Modes define how MyStat determines, displays, and adjusts temperature setpoints. The available temperature adjustment behavior depends on the configured Temperature Mode.
This article describes the temperature-control behavior and adjustment logic for each supported mode. For information about configuring Temperature Modes, refer to Temperature Modes: Overview.
| Supported temperature modes
MyStat supports the following Temperature Modes:
| No. | Temperature Mode | Behavior |
|---|---|---|
1 |
Dual Setpoint Fixed Deadband | Maintains a fixed relationship between the Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT). |
2 |
Dual Setpoint Variable Deadband | Allows HDT and CDT to be adjusted independently while maintaining the minimum required deadband. |
3 |
Single Setpoint | Provides a single user-adjustable temperature setpoint and maintains the corresponding HDT and CDT. |
4 |
Setpoint Offset | Allows the user to adjust temperature relative to the configured baseline comfort setting. |
| Temperature Adjustment Limits
MyStat follows the temperature adjustment limits configured in the system/CCU.
For details about configuring temperature adjustment limits, refer to Temperature Modes: Overview.
| Dual Setpoint Fixed Deadband
In Dual Setpoint Fixed Deadband mode, the Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT) maintain a fixed deadband. When the user adjusts one setpoint, the other setpoint adjusts as required to maintain the configured deadband, subject to the applicable user limits.
Device Display and Temperature Adjustment
To access and adjust the temperature on the MyStat:
- Press Up Arrow button (▲) or Down Arrow button (▼) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the temperature; the display updates to reflect the selected temperature.
Adjustment Range and Formula
The available temperature adjustment on the MyStat is determined by the configured Heating and Cooling User Limits and the applicable deadbands.
The heating and cooling setpoints maintain the following relationship:
CDT − HDT = Heating Deadband + Cooling Deadband
Example :
Initial State
| Parameter | Value |
|---|---|
| HDT | 72°F |
| CDT | 76°F |
| Deadband | 4°F |
User action: Adjust HDT from 72°F to 70°F
Result
| Parameter | Value |
|---|---|
| HDT | 70°F |
| CDT | 74°F |
| Deadband | 4°F |
Therefore, when one setpoint is adjusted, the other setpoint is adjusted as needed to maintain the 4°F deadband while remaining within the configured user limits.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Fixed Deadband.
| Dual Setpoint Variable Deadband
In Dual Setpoint Variable Deadband mode, HDT and CDT can be adjusted independently while maintaining the minimum required deadband. If an adjustment would reduce the difference between HDT and CDT below the configured minimum, the other setpoint adjusts to maintain the required minimum deadband.
Device Display and Temperature Adjustment
To access and adjust the temperature on the MyStat:
- Press Up Arrow button (▲) or Down Arrow button (▼) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Press Menu button to switch between Heating and Cooling temperature adjustment.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the temperature; the display updates to reflect the selected temperature.
Adjustment Range and Formula
The available temperature adjustment on the MyStat is determined by the configured Heating and Cooling User Limits and the applicable deadbands.
The heating and cooling setpoints maintain the following relationship:
CDT − HDT ≥ Heating Deadband (HDB) + Cooling Deadband (CDB)
The user can adjust HDT and CDT independently within the configured user limits. If an adjustment would cause the setpoints to violate the minimum required deadband, the other setpoint automatically adjusts to maintain the required deadband.
Example :
Initial State
| Parameter | Value |
|---|---|
| HDT | 67°F |
| CDT | 77°F |
| Deadband | 4°F |
Scenario 1: Decreasing CDT
User action: Decrease CDT from 77°F to 72°F.
Result:
| Parameter | Value |
|---|---|
| HDT | 67°F |
| CDT | 72°F |
| Deadband | 4°F |
The HDT remains unchanged because the minimum required deadband is maintained.
Scenario 2: Increasing HDT
User action: Increase HDT from 67°F to 70°F.
Result:
| Parameter | Value |
|---|---|
| HDT | 70°F |
| CDT | 74°F |
| Deadband | 4°F |
The CDT automatically adjusts from 72°F to 74°F to maintain the minimum required deadband.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Variable Deadband.
| Single Setpoint
In Single Setpoint mode, the user adjusts a single temperature setpoint. The system uses the configured fixed deadband to determine the corresponding HDT and CDT. When the Single Setpoint changes, HDT and CDT adjust accordingly while maintaining the configured deadband.
Device Display and Temperature Adjustment
To access and adjust the temperature on the MyStat:
- Press Up Arrow button (▲) or Down Arrow button (▼) to access the temperature screen, which displays the Single Setpoint temperature.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the temperature; the display updates to reflect the temperature.
Adjustment Range and Formula
The available temperature adjustment on the MyStat is determined by the configured Heating and Cooling User Limits and applicable deadbands.
In Single Setpoint mode, the user adjusts only the Single Setpoint. The Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT) are calculated based on the Single Setpoint and configured deadbands.
The Single Setpoint maintains the following relationship:
Single Setpoint = HDT + HDB
Single Setpoint = CDT − CDB
When the Single Setpoint is adjusted, the system automatically recalculates the HDT and CDT to maintain the configured fixed deadband.
Example :
Initial State
| Parameter | Value |
|---|---|
| HDT* | 70°F |
| CDT* | 74°F |
| Single Setpoint | 72°F |
| Deadband | 4°F |
User action: Increase the Single Setpoint from 72°F to 74°F
Result
| Parameter | Value |
|---|---|
| HDT* | 72°F |
| CDT* | 76°F |
| Single Setpoint | 74°F |
| Deadband | 4°F |
Note : HDT and CDT are calculated values and are not displayed on the MyStat in Single Setpoint mode.
The Single Setpoint is the user-adjustable value displayed on the device. The system uses it to calculate the corresponding HDT and CDT while maintaining the configured deadband.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Single Setpoint.
| Setpoint Offset
In Setpoint Offset mode, the user adjusts the temperature relative to the baseline comfort setting using a Setpoint Offset value. An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.
Device Display and Temperature Adjustment
When Setpoint Offset mode is configured, the MyStat home screen displays the current Setpoint Offset value and its available range.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the Setpoint Offset value. The displayed offset updates accordingly.
Adjustment Range and Formula
The available Setpoint Offset range on the MyStat is determined by the configured Heating and Cooling User Limits and Heating and Cooling Deadbands.
The Setpoint Offset maintains the following relationship:
Setpoint Offset = HDT + HDB
Setpoint Offset = CDT − CDB
An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Setpoint Offset.