| Overview
Temperature Modes define how the SmartNode determines, displays, and adjusts temperature setpoints. The available temperature adjustment behavior depends on the configured Temperature Mode.
When a MySense is connected to a SmartNode, temperature settings can be viewed and adjusted through the MySense user interface. MySense also provides sensor data to the SmartNode for supported control functions. Depending on the selected Temperature Mode, the temperature interface displayed on the SmartNode and MySense may differ.
This article describes the temperature-control behavior and adjustment logic for each supported mode. For information about configuring Temperature Modes, refer to Temperature Modes: Overview.
| Temperature Mode and Display Behavior
The following table describes the temperature interface displayed on the SmartNode and connected MySense for each Temperature Mode.
| No. | Temperature Mode | UI Visible on SmartNode | UI Visible on MySense |
|---|---|---|---|
1 |
Dual Setpoint Fixed Deadband | Yes | Yes |
2 |
Dual Setpoint Variable Deadband | Yes | Yes |
3 |
Single Setpoint | Dual Setpoint Fixed screen is displayed | Yes |
4 |
Setpoint Offset | Dual Setpoint Fixed screen is displayed | Yes |
Note : For Single Setpoint and Setpoint Offset, the SmartNode uses the Dual Setpoint Fixed screen as part of the underlying temperature-control flow, while MySense provides the corresponding user interface for the selected mode.
| Temperature Adjustment Limits
SmartNode follows the temperature adjustment limits configured in the system/CCU.
For details about configuring temperature adjustment limits, refer to Temperature Modes: Overview.
| Dual Setpoint Fixed Deadband
In Dual Setpoint Fixed Deadband mode, the Heating Desired Temperature (HDT) and Cooling Desired Temperature (CDT) maintain a fixed deadband. When the user adjusts one setpoint, the other setpoint adjusts as required to maintain the configured deadband, subject to the applicable user limits.
Device Display and Temperature Adjustment
To access and adjust the temperature on the SmartNode:
- Press Up button or Down button to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Use Up button and Down button to increase or decrease the temperature; the display updates to reflect the selected temperature.
To access and adjust the temperature on the MySense:
- Press Up Arrow button (▲) or Down Arrow button (▼) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the temperature; the display updates to reflect the selected temperature.
Adjustment Range and Formula
The available temperature adjustment is determined by the configured Heating and Cooling User Limits and the applicable deadbands.
The heating and cooling setpoints maintain the following relationship:
CDT − HDT = Heating Deadband + Cooling Deadband
Example :
SmartNode-UI MySense-UI
Initial State
| Parameter | Value |
|---|---|
| HDT | 72°F |
| CDT | 76°F |
| Deadband | 4°F |
User action: Adjust HDT from 72°F to 70°F
SmartNode-UI MySense-UI
Result
| Parameter | Value |
|---|---|
| HDT | 70°F |
| CDT | 74°F |
| Deadband | 4°F |
The CDT automatically adjusts to maintain the configured deadband.
Therefore, when one setpoint is adjusted, the other setpoint is adjusted as needed to maintain the 4°F deadband while remaining within the configured user limits.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Fixed Deadband.
| Dual Setpoint Variable Deadband
In Dual Setpoint Variable Deadband mode, HDT and CDT can be adjusted independently while maintaining the minimum required deadband. If an adjustment would reduce the difference between HDT and CDT below the configured minimum, the other setpoint adjusts to maintain the required minimum deadband.
Device Display and Temperature Adjustment
To access and adjust the temperature on the SmartNode:
- Press Up button or Down button to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Press Left or Right button to switch between Heating and Cooling temperature adjustment.
- Use Up button and Down button to increase or decrease the temperature; the display updates to reflect the selected temperature.
To access and adjust the temperature on the MySense:
- Press Up Arrow button (▲) or Down Arrow button (▼) to access the temperature screen, which displays the Cooling Desired and Heating Desired temperatures.
- Press Menu button to switch between Heating and Cooling temperature adjustment.
- Use Up Arrow button (▲) and Down Arrow button (▼) to increase or decrease the temperature; the display updates to reflect the selected temperature.
Adjustment Range and Formula
The available temperature adjustment is determined by the configured Heating and Cooling User Limits and the applicable deadbands.
The heating and cooling setpoints maintain the following relationship:
CDT − HDT ≥ Heating Deadband (HDB) + Cooling Deadband (CDB)
The user can adjust HDT and CDT independently within the configured user limits. If an adjustment would cause the setpoints to violate the minimum required deadband, the other setpoint automatically adjusts to maintain the required deadband.
Example :
SmartNode-UI MySense-UI
Initial State
| Parameter | Value |
|---|---|
| HDT | 67°F |
| CDT | 77°F |
| Deadband | 4°F |
Scenario 1: Decreasing CDT
User action : Decrease CDT from 77°F to 72°F.
SmartNode-UI MySense-UI
Result:
| Parameter | Value |
|---|---|
| HDT | 67°F |
| CDT | 72°F |
| Deadband | 4°F |
The HDT remains unchanged because the minimum required deadband is maintained.
Scenario 2: Increasing HDT
User action : Increase HDT from 67°F to 70°F.
SmartNode-UI MySense-UI
Result:
| Parameter | Value |
|---|---|
| HDT | 70°F |
| CDT | 74°F |
| Deadband | 4°F |
The CDT automatically adjusts from 72°F to 74°F to maintain the minimum required deadband.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Dual Setpoint Variable Deadband.
| Single Setpoint
In Single Setpoint mode, the user adjusts a single temperature setpoint. The system uses the configured fixed deadband to determine the corresponding HDT and CDT. When the Single Setpoint changes, HDT and CDT adjust accordingly while maintaining the configured deadband.
Device Display and Temperature Adjustment
When Single Setpoint mode is configured, the SmartNode displays the Dual Setpoint Fixed temperature screen, while MySense displays the current Single Setpoint.
To access and adjust the temperature on the SmartNode and MySense:
- Press the Up button or Down button on the SmartNode, or use the Up Arrow button (▲) or Down Arrow button (▼) on MySense to access and adjust the temperature.
Note : Temperature changes are synchronized between the SmartNode and MySense. When the temperature is adjusted on either device, the system automatically calculates the corresponding value and updates the display on the other device.
Adjustment Range and Formula
The available temperature adjustment is determined by the configured Heating and Cooling User Limits and applicable deadbands.
In Single Setpoint mode, the user adjusts the Temperature on either the SmartNode or MySense. The system automatically calculates the corresponding temperature values and synchronizes the updated value between the SmartNode and MySense.
The Single Setpoint maintains the following relationship:
Single Setpoint = HDT + HDB
Single Setpoint = CDT − CDB
When the Single Setpoint is adjusted, the system automatically recalculates the HDT and CDT to maintain the configured fixed deadband.
Example :
SmartNode-UI MySense-UI
Initial State
| Parameter | Value |
|---|---|
| HDT* | 70°F |
| CDT* | 74°F |
| Single Setpoint | 72°F |
| Deadband | 4°F |
User action : Increase the Single Setpoint from 72°F to 74°F.
SmartNode-UI MySense-UI
Result
| Parameter | Value |
|---|---|
| HDT* | 72°F |
| CDT* | 76°F |
| Single Setpoint | 74°F |
| Deadband | 4°F |
Note : HDT and CDT are calculated values and are not displayed on the MySense in Single Setpoint mode.
The Single Setpoint is the user-adjustable value displayed on MySense. The system uses it to calculate the corresponding HDT and CDT displayed on SmartNode while maintaining the configured deadband.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Single Setpoint.
| Setpoint Offset
In Setpoint Offset mode, the user adjusts the temperature relative to the baseline comfort setting using a Setpoint Offset value. An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.
Device Display and Temperature Adjustment
When Single Setpoint mode is configured, the SmartNode displays the Dual Setpoint Fixed temperature screen, while MySense displays the Setpoint Offset Value on the home Screen.
To access and adjust the temperature on the SmartNode and MySense:
- Press the Up button or Down button on the SmartNode, or use the Up Arrow button (▲) or Down Arrow button (▼) on MySense to adjust the Setpoint Offset value.
- The Setpoint Offset value is synchronized between the SmartNode and MySense, with the corresponding value automatically updated on the other device.
Note: The Setpoint Offset value is synchronized between the SmartNode and MySense. When the Setpoint Offset is adjusted on either device, the system automatically calculates the corresponding temperature value and updates the display on the other device.
Adjustment Range and Formula
The available Setpoint Offset range is determined by the configured Heating and Cooling User Limits and Heating and Cooling Deadbands.
The Setpoint Offset maintains the following relationship:
Setpoint Offset = HDT + HDB
Setpoint Offset = CDT − CDB
An offset of 0 represents the baseline comfort setting. Positive offset values represent a warmer temperature preference, while negative offset values represent a cooler temperature preference.
For detailed information about user limits, deadbands, and temperature range calculations, refer to Temperature Mode: Setpoint Offset.