The 75F Hyperstat can control compatible single-zone or multi-zone Carrier split systems by using the KSAIC0301230 24V interface kit for ductless and hybrid solutions. 

 

Scenario:

Several non-ducted Carrier split systems are installed throughout an open office space with an existing 75F system. 

 

How does it work:

The Hyperstat is paired to the CCU utilizing the Conventional Package Unit (CPU) and configured for single-stage operation 1- Cool 1-Heat 1-Fan. The Hyperstat, indoor and outdoor units are wired to the 24v interface module. If wired correctly, the interface module will display 00- indicating the interface module is successfully powered up and the system is on standby. When the Hyperstat calls for conditioning the three-segment LCD on the interface module will display 01-Cooling Operation, 02- Heating Operation, and 03- Fan Only Operation. 

 

Wiring and Configuration :

 

Note: Please reference the indoor/outdoor unit compatibility chart to verify the KSAIC0301230 24v interface is compatible with your equipment.

https://www.shareddocs.com/hvac/docs/1011/Public/0C/CAR-DLSS-04CC.pd

https://www.shareddocs.com/hvac/docs/1010/Public/01/01-DLS-043-01.pdf

 

Please pay close attention to the installation manual for your indoor unit, outdoor unit, and 24v Interface.

24v Interface Installation Manual https://ca-manufacturer-documents.s3.amazonaws.com/CarrierDocs/IM-KSAIC03-08.pdf

 

The communications wiring S1(P) S2(Q) for the indoor and outdoor units to the 24v interface module must be two conductor-stranded 16ga shielded. The connection is polarity sensitive, both shields (bare wire) are twisted together at the interface module and grounded at the indoor and outdoor units. Dip switches SW1-1 and SW1-2 at the interface are set in the ON position all the other dip switches are set to the OFF position. Please take a look at the wiring detail and configuration below.

 

Screenshot 2023-12-05 at 2.05.28 PM (2).png

75F Configuration:

Screenshot 2023-12-05 at 2.01.01 PM (2).png

Result:

In addition to unit control, the Hyperstat adds the ability to monitor indoor air quality (IAQ) utilizing the onboard CO2 (ppm), VOC (ppb), and humidity (RH%) sensors. There are additional sensors available such as sound (dB), Illuminance (lux), and occupancy which can be used for advanced energy-saving zone control.